Product Line: Hazardous Location (Titan N)
Duty: General Duty (Suitable For Some Hazardous Locations and Marine ABS Duty)
Phase: 3
Rating: 45kVA
Primary Connection: Delta
Primary Voltage: 480D
Primary BIL: 10kV
Primary FCAN (NPL): 2x2.5%
Primary FCBN (NPL): 4x2.5%
Secondary Connection: Wye-N
Secondary Voltage: 208Y/120
Secondary BIL: 10kV
Material: Copper
Frequency: 60Hz
Vector Configuration: Dyn1 (-30°) Ambient
Temp Rating: 40°C (40°C avg, 50°C max over 24hr period)
Temperature Rise: 115°C
Insulation Class: 180°C
Efficiency Regulation: No
Efficiency Specification Sound Level: 50dBA (CSA C-9)
Impedance (Std): 2% - 5%
Approval: cULus (Class 1, Division 2, Groups A,B,C,D and Class I, Zone 2, Group IIC, T3 Hazardous Location), ABS Shield: Single Seismic
Compliance: OSHPD, IBC 2018 (Sds=2.0, z/h=1, lp=1.5)
Nameplate: HPS
Standard Cooling: ANC
Primary Termination (NPL): Mounting Pads Secondary
Termination (NPL): Mounting Pads Enclosure
Type*: Type 4X / IP66
Enclosure Finish: Stainless Steel 316 Polished
Enclosure PN (NPL): DQT6-N4X
Enclosure Dimensions (H/W/D): 21.88in(H), 26.13in(W), 19.75in(D)
Net Weight: 695 lb
DC fuse, EV fuse, high speed fuse, current limiting fuse cross reference.