Your Trusted Source for Industrial Electrical Components

AHR 1500 B420

Current Transducer

LEM | AHR-Series | EN 50178 | Panel Mount

1500 ANominal Primary Current
1) +20 ... 50 V DCPower Supply
DC 20 … 6000 HzBandwidth (-1dB)
5.8 kVRMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud
11.9 mmCreepage Distance (dCp)

Additional Technical Details

View Full Specifications
Primary Current, Measuring Range2500 A
Supply Voltage1) +20 ... 50 V DC
Operating Temperature Range−40 … +70 °C
Isolation Test Voltage5.8 kV
Primary Nominal RMS Current (IPN)1500 A
Current Consumption (IC)30 mA + I

Standards & Approvals

  • EN 50178: 1997

Typical Applications

AC power supplies or Motors: True RMS current sensing - the most accurate way to monitor power supply or motor input power, VFD Controlled Loads: VFD output current monitoring attached load are operating, SCRs or Swith-mode Rectifiers: Accurate measurement of output current, Renewable Energy Installations Continuous condition minitoring allowing automatic failure detection/ anticipation.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The AHR 1500 B420 is a None current transducer from LEM.

Typical applications include AC power supplies or Motors: True RMS current sensing - the most accurate way to monitor power supply or motor input power, VFD Controlled Loads: VFD output current monitoring attached load are operating, SCRs or Swith-mode Rectifiers: Accurate measurement of output current and Renewable Energy Installations Continuous condition minitoring allowing automatic failure detection/ anticipation.

Key characteristics from the official datasheet: frequency bandwidth DC 20 … 6000 Hz; operating temperature −40 … +70 °C.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesAHR
Product ReferenceAHR 1500 B420
Primary Nominal Current1500 A
Supply Voltage1) +20 ... 50 V DC
Measurement—
MountingPanel Mount
Application DomainEnergy solutions
Electrical Data — AHR 1500 B420
Primary Nominal RMS Current (IPN)1500 A
Primary Current, Measuring Range (IPM)2500 A
Supply Voltage (UC)1) +20 ... 50 V DC
Current Consumption (IC)30 mA + I
Accuracy & Dynamic Performance
Frequency Bandwidth (BW)DC 20 … 6000 Hz
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud5.8 kV
Creepage Distance (dCp)11.9 mm
Clearance (dCI)11.9 mm
Comparative Tracking Index (CTI)225
Rated Insulation Voltage (basic)1000 V
Rated Insulation Voltage (reinforced)500 V
Overvoltage Category / Pollution DegreeOver voltage category OV · Pollution degree PD2
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)−40 … +70 °C
Ambient Storage Temperature (TA st)−40 … +85 °C
Mass (m)650 g
Case MaterialInsulating plastic case recognized according to UL 94-V0.
General Tolerance±1.0 mm
Standards & Certifications
EN 501781997

Note: Specifications are taken from the official AHR 1500 B420 datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the AHR 1500 B420 are shown below.

AHR 1500 B420 outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM AHR 1500 B420 datasheet
Outline Dimensions & Mechanical Data
General Tolerance±1.0 mm
Mass650 g
Case MaterialInsulating plastic case recognized according to UL 94-V0.

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the AHR 1500 B420.

AC power supplies or Motors: True RMS current sensing - the most accurate way to monitor power supply or motor input power
VFD Controlled Loads: VFD output current monitoring attached load are operating
SCRs or Swith-mode Rectifiers: Accurate measurement of output current
Renewable Energy Installations Continuous condition minitoring allowing automatic failure detection/ anticipation

Characteristic Curves

Characteristic curve diagrams are not included in the AHR 1500 B420 datasheet; the relevant characteristics are the accuracy and dynamic performance data listed below.

Accuracy & Dynamic Characteristics
Frequency Bandwidth (BW)DC 20 … 6000 Hz

Note: For the full set of performance data, refer to the datasheet.