Your Trusted Source for Industrial Electrical Components

AP 400 B420L

AC Current Transducer

LEM | AP-Series | Panel Mount

(loop powered) +12 … 24 V DCPower Supply
30 … 2000 HzBandwidth (-1dB)
< ± 1 % of ITotal Error @ IPN
30 .. 2000 HzBW Frequency bandwidth (± 1 %)
2000 HzBW Frequency bandwidth (±1 %) 30 …

Additional Technical Details

View Full Specifications
Supply Voltage(loop powered) +12 … 24 V DC
Isolation Test Voltage4.13 kV
Supply Output voltage current (loop limitation powered) 2) +12 … (UI)24 < 25 V DC mA
Output current limitation (I)< 25 mA
Frequency Bandwidth (BW)30 … 2000 Hz
Response time to 90 % of I step (t)< 150 ms

Standards & Approvals

Typical Applications

Automation systems Analog current reading for remote systems monitoring (e.g. motor) and Analog current reading for remote sotware alarms. monitoring (e.g. motor) and, Panel meters software alarms. Simple connection to power meters consumption displays. Simple connection to power

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The AP 400 B420L is a None current transducer from LEM delivering a output current limitation (i) of < 25 mA.

Typical applications include Automation systems Analog current reading for remote systems monitoring (e.g. motor) and Analog current reading for remote sotware alarms. monitoring (e.g. motor) and and Panel meters software alarms. Simple connection to power meters consumption displays. Simple connection to power.

Key characteristics from the official datasheet: total error < ± 1 % of I; frequency bandwidth 30 … 2000 Hz.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesAP
Product ReferenceAP 400 B420L
Supply Voltage(loop powered) +12 … 24 V DC
Measurement—
MountingPanel Mount
Application DomainEnergies, Automation. domain and Automation
Electrical Data — AP 400 B420L
Supply Voltage (UC)(loop powered) +12 … 24 V DC
Supply voltage (loop powered) (V)+ 12 .. 24 V
Supply Output voltage current (loop limitation powered) 2) +12 … (UI)24 < 25 V DC mA
Output current limitation (I)< 25 mA
Accuracy & Dynamic Performance
Total Error (εtot) @ IPN< ± 1 % of I
Frequency Bandwidth (BW)30 … 2000 Hz
Response time to 90 % of I step (t)< 150 ms
BW Frequency bandwidth (± 1 %)30 .. 2000 Hz
BW Frequency bandwidth (±1 %) 30 …2000 Hz
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud4.13 kV
Impulse Withstand Voltage (1.2/50 µs) UNi6.1 kV
Creepage Distance (dCp)5.5 mm
Comparative Tracking Index (CTI)600
Overvoltage Category / Pollution DegreeOver voltage category CAT · Pollution degree PD2
Rated insulation RMS voltage (U)300 V
RMS voltage for AC insulation test 3) 50 Hz (U)1 min 4.13 kV
Partial discharge test voltage (q < 10 pC) (U)1.5 kV
Impulse withstand voltage 1.2/50 (U)µs 6.1 kV
Creepage distance (d)5.5 mm
Clearance4) (d)5.5 mm
Comparative tracking index (Group I)600
Route du Nant-d’Avril152
Environmental & Mechanical Characteristics
Case MaterialInsulating plastic case recognized according to UL 94-V0.
Ambient operating temperature −20 … (T)+60 °C
Ambient storage temperature −20 … (T)+85 °C
RH Relative Humidity (non-condensing)≤ 85 %
Altitude above sea level (indoor use only)2000 m
Mass (m)90 g
IPxx Protection degree IP20

Note: Specifications are taken from the official AP 400 B420L datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the AP 400 B420L are shown below.

AP 400 B420L outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM AP 400 B420L datasheet, page 4
Outline Dimensions & Mechanical Data
Case MaterialInsulating plastic case recognized according to UL 94-V0.
IPxx Protection degree IP20

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the AP 400 B420L.

Automation systems Analog current reading for remote systems monitoring (e.g. motor) and Analog current reading for remote sotware alarms. monitoring (e.g. motor) and
Panel meters software alarms. Simple connection to power meters consumption displays. Simple connection to power

Characteristic Curves

Characteristic curve diagrams are not included in the AP 400 B420L datasheet; the relevant characteristics are the accuracy and dynamic performance data listed below.

Accuracy & Dynamic Characteristics
Total Error (εtot) @ IPN< ± 1 % of I
Frequency Bandwidth (BW)30 … 2000 Hz
Response time to 90 % of I step (t)< 150 ms
BW Frequency bandwidth (± 1 %)30 .. 2000 Hz
BW Frequency bandwidth (±1 %) 30 …2000 Hz

Note: For the full set of performance data, refer to the datasheet.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment