Your Trusted Source for Industrial Electrical Components

ART-B22-D125/SP25 3m, SMA

Flexible clip-around Rogowski coil current sensor

LEM | ART-Series | IEC 61010-1 | Busbar Mount

Any current (no saturation)Nominal Primary Current
RogowskiTechnology
420 kHzBandwidth (-3dB)
NoneLinearity Error (Max)
AC 1000 V, 50/60 Hz, CAT III, 2000 ARated Insulation Voltage

Additional Technical Details

View Full Specifications
Operating Temperature Range−40 ... 80 °C
Isolation Test Voltage7.4 kV
Frequency Bandwidth420 kHz
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud7.4 kV
Impulse Withstand Voltage (1.2/50 µs) UNi12.8 kV
Comparative Tracking Index (CTI)600

Standards & Approvals

  • IEC 61010-1
  • IEC 61010-2-32
  • IEC 61869-10: 2017 1)
  • UL 61010-1: 2012

Typical Applications

Secondary distribution substations, Distribution transformer monitoring, Phasor Measurement Units (PMU), Commercial and industrial buildings, Metering and sub-metering, Demand response (DR), Distribution system equipment.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The ART-B22-D125/SP25 3m, SMA is a flexible clip-around Rogowski coil current sensor from LEM for the electronic measurement of AC current, with galvanic isolation, delivering an instantaneous output voltage of 22.5 mV/kA @ 50 Hz, IP = 1 kA.

Since it cannot saturate, very high and short-circuit currents are measured without degradation. Typical applications include Secondary distribution substations, Distribution transformer monitoring, Phasor Measurement Units (PMU) and Commercial and industrial buildings.

Key characteristics from the official datasheet: frequency bandwidth 420 kHz; operating temperature −40 ... 80 °C.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesART
Product ReferenceART-B22-D125/SP25 3m, SMA
Primary Nominal CurrentAny current (no saturation)
MeasurementAC current (flexible Rogowski coil)
Sensing Aperture⌀ 125 mm
Application DomainsIndustrial · Smart Grid
Electrical Data — ART-B22-D125/SP25 3m, SMA (TA = 25 °C, RL = 10 kΩ)
Primary Nominal Current (IPr)Not applicable (no saturation)
Rated Short-time Thermal Current (Ith)300 kA @ 50 Hz
Rated Transformation Ratio (kr)44.44 kA/V @ 50 Hz
Rated Frequency (fr)50/60 Hz
Secondary Voltage (US)22.5 mV/kA @ 50 Hz, IP = 1 kA
Mutual Inductance (M)71.98 nH
Temperature Coefficient of M (TCM)±30 ppm/K
Frequency Bandwidth (BW, −3 dB)420 kHz (cable length 3 m)
Phase Displacement (Δφ) @ 50/60 Hz0.004 °
Coil Inductance (LS)258 µH
Coil Resistance (RS)81 Ω
Ratio Error (ε, centered)−0.5 … +0.5 %
Ratio Error (ε, all positions)−0.75 … +0.75 % (including positioning error)
Linearity Error (εL)None
Error due to External Magnetic Field (εI ext)0 ±0.2 ±0.4 %
Absolute Maximum Ratings
Maximum Secondary Voltage US max30 V
Maximum Primary Conductor Temperature TB max105 °C
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud7.4 kV
Impulse Withstand Voltage (1.2/50 µs) UNi12.8 kV
Partial Discharge RMS Test Voltage (q < 10 pC) Ut1.65 kV
Clearance (pri. – sec.) dCI> 16 mm
Creepage Distance (pri. – sec.) dCp> 16 mm
Case MaterialV0 (according to UL 94)
Comparative Tracking Index CTI600
Rated Insulation Voltage (UL 61010-1)AC 1000 V, 50/60 Hz, CAT III, 2000 A
Overvoltage Category / Pollution DegreeCAT IV, PD2 (reinforced) · CAT III, PD2 (basic)
Environmental & Mechanical Characteristics
Ambient Operating Temperature TA−40 … +80 °C
Ambient Storage Temperature TA st−40 … +80 °C
Relative Humidity (non-condensing) RH0 … 90 %
Altitude above Sea Level2000 m
Protection DegreeIP57
Mass (⌀ 125 mm)200 g (cable length 3 m)
Output Cable Length3 m
Termination2 stripped wires
General Tolerance±1 mm
Standards & Certifications
IEC 61010-12010
IEC 61010-2-322012
IEC 61869-102017 – Class 0.5 accuracy
UL 61010-12012 (Third Edition), File # E330077, Vol. D1
CAN/CSA-C22.2 No. 61010-1-123rd Edition (revision 2016)

Note: Specifications are taken from the official ART-B22-D125/SP25 3m, SMA datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the ART-B22-D125/SP25 3m, SMA are shown below.

ART-B22-D125/SP25  3m, SMA outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM ART-B22-D125/SP25 3m, SMA datasheet
Outline Dimensions & Mechanical Data
Mass200 g
Case MaterialV0 (according to UL 94)
Protection DegreeIP57
Output Cable Length3 m
Termination2 stripped wires
General Tolerance±1 mm

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the ART-B22-D125/SP25 3m, SMA.

Secondary distribution substations
Distribution transformer monitoring
Phasor Measurement Units (PMU)
Commercial and industrial buildings
Metering and sub-metering
Demand response (DR)
Distribution system equipment

Characteristic Curves

The accuracy class characteristic diagram of the ART-B22-D125/SP25 3m, SMA from the official datasheet is shown below.

ART-B22-D125/SP25  3m, SMA accuracy class characteristic diagram
Accuracy class characteristic diagram — source: LEM ART-B22-D125/SP25 3m, SMA datasheet
Accuracy & Dynamic Characteristics
Secondary Voltage (US)22.5 mV/kA @ 50 Hz, IP = 1 kA
Mutual Inductance (M)71.98 nH
Temperature Coefficient of M (TCM)±30 ppm/K
Frequency Bandwidth (BW, −3 dB)420 kHz (cable length 3 m)
Phase Displacement (Δφ) @ 50/60 Hz0.004 °
Ratio Error (ε, centered)−0.5 … +0.5 %
Ratio Error (ε, all positions)−0.75 … +0.75 % (including positioning error)
Linearity Error (εL)None
Error due to External Magnetic Field (εI ext)0 ±0.2 ±0.4 %
Reference Conditions
Ambient Temperature (TA)25 °C, unless otherwise noted
Rated Frequency (fr)50/60 Hz

Note: For the full set of performance data, refer to the datasheet.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment