Your Trusted Source for Industrial Electrical Components
Home Products LEM Automotive Series DCBM Series DCBM_N00_6000C20_0000C00

DCBM_N00_6000C20_0000C00

direct connected energy meter dedicated to DC applications

LEM | DCBM-Series | EN 50470-1 | DIN rail 35 mm and screw mounting

600 ANominal Primary Current
+12 ... +48 V DCPower Supply
1000 VRated Operational Voltage
18 kARated Withstand Peak Current (IP max)
10 WInsertion Loss in Current Path

Additional Technical Details

View Full Specifications
Rated Conventional Thermal Current600 A
Accuracy ClassB
Reference Voltage (Uref)150 ... 1000 V DC
Auxiliary Power Supply+12 ... +48 V DC
Operating Temperature Range−40 .. +85 °C
Ingress Protection RatingIP10

Standards & Approvals

  • EN 50470-1: 2006
  • EN 50470-3: 2006
  • PTB-A 50.7
  • PTB-A 20.1
  • Directive 2014/32/EU (MID)
  • Regulation n° 22.00.570.001.1 (France)
  • IEC 62052-11: 2003
  • IEC 61000-6-2: 2016
  • IEC 61000-6-3: 2016
  • UL 61010-1: 2012/A1:2019
  • UL 61010-2-030:2018

Typical Applications

Electric Vehicle Charging infrastructures, Data centers, DC grids & Energy Monitoring, Energy storage, renewables.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The DCBM_N00_6000C20_0000C00 is a None current transducer from LEM for the electronic measurement of direct connected energy meter dedicated to DC applications.

The accuracy class is B. Typical applications include Electric Vehicle Charging infrastructures, Data centers, DC grids & Energy Monitoring and Energy storage, renewables.

Key characteristics from the official datasheet: operating temperature −40 .. +85 °C.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesDCBM
Product ReferenceDCBM_N00_6000C20_0000C00
Primary Nominal Current600 A
Supply Voltage+12 ... +48 V DC
Measurementdirect connected energy meter dedicated to DC applications
MountingDIN rail 35 mm and screw mounting
Application DomainElectric Vehicle Charging infrastructures, Data centers, DC grids & Energy Monitoring, Energy storage, renewables
Electrical Data — DCBM_N00_6000C20_0000C00
Rated Conventional Thermal Current600 A
Rated Operational Voltage1000 V
Rated Withstand Peak Current (IP max)18 kA
Insertion Loss in Current Path10 W
Power Consumption in Voltage Path0.13 W
Supply Voltage (UC)+12 ... +48 V DC
Supply Current (IC)400 mA @ +12 V DC
Energy Measurement & Accuracy
Accuracy ClassB
Meter Typedirect connected energy meter dedicated to DC applications
Starting Current (Ist)480 mA
Minimum Current (Imin)6 A
Transitional Current (Itr)12 A
Reference Current (Iref)120 A
Maximum Current (Imax)600 A
Reference Voltage (Uref)150 ... 1000 V DC
Maximum Limit Range of Operation1100 V DC
Minimum Limit Range of Operation135 V DC
Energy Registering Resolution0.1 Wh
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud4400 V
Impulse Withstand Voltage (1.2/50 µs) UNi8 kV
Rated Insulation Voltage1000 V DC
Pollution Degree2
Rated Altitude2000 m
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)−40 .. +85 °C
Ambient Storage Temperature (TA st)−40 .. +85 °C
Mass (m)415 g
Case MaterialV0
Ingress Protection RatingIP10
Impact RatingIK05
MountingDIN rail 35 mm and screw mounting
Standards & Certifications
EN 50470-12006
EN 50470-32006
PTB-A 50.7
PTB-A 20.1
Directive 2014/32/EU (MID)
Regulation n° 22.00.570.001.1 (France)
IEC 62052-112003
IEC 61000-6-22016
IEC 61000-6-32016
UL 61010-12012/A1:2019
UL 61010-2-0302018

Note: Specifications are taken from the official DCBM_N00_6000C20_0000C00 datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the DCBM_N00_6000C20_0000C00 are shown below.

DCBM_N00_6000C20_0000C00 outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM DCBM_N00_6000C20_0000C00 datasheet
Outline Dimensions & Mechanical Data
Mass415 g
Case MaterialV0
Ingress Protection RatingIP10

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the DCBM_N00_6000C20_0000C00.

Electric Vehicle Charging infrastructures
Data centers
DC grids & Energy Monitoring
Energy storage, renewables

Characteristic Curves

Characteristic curve diagrams are not included in the DCBM_N00_6000C20_0000C00 datasheet; the relevant characteristics are the accuracy and dynamic performance data listed below.

Accuracy & Dynamic Characteristics
Accuracy ClassB
Reference Conditions
Ambient Temperature (TA)25 °C, unless otherwise noted
Accuracy ClassB

Note: For the full set of performance data, refer to the datasheet.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment