Your Trusted Source for Industrial Electrical Components
Home Products LEM Automotive Series HAH Series HAH3DR 800-S06

HAH3DR 800-S06

Open Loop transducer using the Hall effect

LEM | HAH-Series | Open Loop Transducer | Busbar Mount

± 800 ANominal Primary Current
4.75 .. 5.25 VPower Supply
Open Loop TransducerTechnology
40 kHzBandwidth (-1dB)
± 1 %Linearity Error (Max)

Additional Technical Details

View Full Specifications
Primary Current, Measuring Range± 800 A
Supply Voltage4.75 .. 5.25 V
Sensitivity2.5 mV/A
Operating Temperature Range−40 .. 125 °C
Isolation Test Voltage2.5 kV
Primary Nominal Current (IPN)± 800 A

Standards & Approvals

Typical Applications

Unsealed connector. a constant.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Technical Specifications

General Information
ManufacturerLEM
Product SeriesHAH
Product ReferenceHAH3DR 800-S06
Primary Nominal Current± 800 A
Supply Voltage4.75 .. 5.25 V
Measurement—
MountingBusbar Mount
Application DomainUnsealed connector. a constant
Electrical Data — HAH3DR 800-S06
Primary Nominal Current (IPN)± 800 A
Primary Current, Measuring Range (IPM)± 800 A
Supply Voltage (UC)4.75 .. 5.25 V
Current Consumption (IC)44 .. 50 mA
Sensitivity2.5 mV/A
Output Offset Voltage (VO E)2.5 V
Load Resistance (RL)10 kOhm
Insulation Resistance (RINS)500 MOhm
Accuracy & Dynamic Performance
Ratiometricity Error0.6 %
Sensitivity Error± 1 %
Linearity Error± 1 %
Delay Time (tD)4 .. 6 µs
Frequency Bandwidth40 kHz
Output Noise10 mV
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud2.5 kV
Comparative Tracking Index (CTI)PLC3 (175 V to 249 V) Typica
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)−40 .. 125 °C
Ambient Storage Temperature (TA st)−50 .. 125 °C
Mass (m)137 g

Note: Specifications are taken from the official HAH3DR 800-S06 datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the HAH3DR 800-S06 are shown below.

HAH3DR 800-S06 outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM HAH3DR 800-S06 datasheet
Outline Dimensions & Mechanical Data
Mass137 g

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the HAH3DR 800-S06.

Unsealed connector. a constant

Characteristic Curves

The characteristic curves of the HAH3DR 800-S06 from the official datasheet are shown below.

HAH3DR 800-S06 characteristic curves
Characteristic curves — source: LEM HAH3DR 800-S06 datasheet
Accuracy & Dynamic Characteristics
Sensitivity2.5 mV/A
Sensitivity Error± 1 %
Linearity Error± 1 %
Frequency Bandwidth40 kHz
Reference Conditions
Ambient Temperature (TA)25 °C, unless otherwise noted
Output Load Resistance (RL)10 kOhm

Note: Refer to the datasheet for the complete set of characteristic curves.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment