Your Trusted Source for Industrial Electrical Components

HAT 800-S

Hall effect measuring principle

LEM | HAT-Series | EN 50178 | Busbar Mount

800 ANominal Primary Current
±15 VPower Supply
DC ... 25 kHzBandwidth (-1dB)
±1 %Linearity Error (Max)
> 1000 MΩInsulation Resistance (RINS)

Additional Technical Details

View Full Specifications
Primary Current, Measuring Range±2400 A
Supply Voltage±15 V
Operating Temperature Range−40 ... +105 °C
Isolation Test Voltage4.9 kV
Primary Nominal RMS Current (IPN)800 A
Current Consumption (IC)±20 mA

Standards & Approvals

  • EN 50178
  • UL 508: 2010 5)

Typical Applications

DC motor drives, Switched Mode Power Supplies (SMPS), AC variable speed drives, Uninterruptible Power Supplies (UPS), Battery supplied applications, Power supplies for welding applications.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The HAT 800-S is a None current transducer from LEM for the electronic measurement of currents: DC, AC, pulsed,..., U = ±4 V, with galvanic isolation.

Typical applications include DC motor drives, Switched Mode Power Supplies (SMPS), AC variable speed drives and Uninterruptible Power Supplies (UPS).

Key characteristics from the official datasheet: linearity error ±1 %; frequency bandwidth DC ... 25 kHz; operating temperature −40 ... +105 °C.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesHAT
Product ReferenceHAT 800-S
Primary Nominal Current800 A
Supply Voltage±15 V
Measurementcurrents: DC, AC, pulsed,..., U = ±4 V
MountingBusbar Mount
Application DomainIndustrial
Electrical Data — HAT 800-S
Primary Nominal RMS Current (IPN)800 A
Primary Current, Measuring Range (IPM)±2400 A
Supply Voltage (UC)±15 V
Current Consumption (IC)±20 mA
Insulation Resistance (RINS)> 1000 MΩ
Accuracy & Dynamic Performance
Linearity Error (εL) (0 ... ±IPN)±1 %
Frequency Bandwidth (−3 dB)DC ... 25 kHz
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud4.9 kV
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)−40 ... +105 °C
Ambient Storage Temperature (TA st)−40 ... +105 °C
Mass (m)300 g
Case MaterialInsulating plastic case recognized according to UL 94-V0.
General Tolerance±1 mm
Standards & Certifications
EN 50178Compliance
UL 5082010 5)

Note: Specifications are taken from the official HAT 800-S datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the HAT 800-S are shown below.

HAT 800-S outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM HAT 800-S datasheet, page 3
Outline Dimensions & Mechanical Data
General Tolerance±1 mm
Mass300 g
Case MaterialInsulating plastic case recognized according to UL 94-V0.

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the HAT 800-S.

DC motor drives
Switched Mode Power Supplies (SMPS)
AC variable speed drives
Uninterruptible Power Supplies (UPS)
Battery supplied applications
Power supplies for welding applications

Characteristic Curves

Characteristic curve diagrams are not included in the HAT 800-S datasheet; the relevant characteristics are the accuracy and dynamic performance data listed below.

Accuracy & Dynamic Characteristics
Linearity Error (εL) (0 ... ±IPN)±1 %
Frequency Bandwidth (−3 dB)DC ... 25 kHz

Note: For the full set of performance data, refer to the datasheet.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment