LF 510-S/SP22

Closed loop (compensated)

LEM | LF-Series | Closed loop (compensated) | EN 50155 | Panel Mount

500 ANominal Primary Current
±14.25 .. ±25.2 VPower Supply
Closed loop (compensated)Technology
200 kHzBandwidth (-1dB)
± 0.5 % (25 … 70 °C) / ± 0.6 % (−40 … 70 °C)Total Error @ IPN

Additional Technical Details

View Full Specifications
Primary Current, Measuring Range0 .. ± 1200 A
Secondary Nominal Current0.1429 A
Supply Voltage±14.25 .. ±25.2 V
Operating Temperature Range−40 … 70 °C
Isolation Test Voltage4 kV
Primary Nominal RMS Current (IPN)500 A

Standards & Approvals

  • EN 50155: 2021
  • EN 50124-1: 2017
  • EN 50121-3-2: 2016
  • UL 508: 2010

Typical Applications

Single or three phase inverters, Propulsion and braking choppers, Propulsion converters, Auxiliary converters, Battery chargers, Substations.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The LF 510-S/SP22 is a closed loop (compensated) current transducer from LEM for the electronic measurement of current: DC, AC, pulsed..., with galvanic isolation.

Typical applications include Single or three phase inverters, Propulsion and braking choppers, Propulsion converters and Auxiliary converters.

Key characteristics from the official datasheet: total error ± 0.5 % (25 … 70 °C) / ± 0.6 % (−40 … 70 °C); linearity error ± 0.1 %; frequency bandwidth 200 kHz; operating temperature −40 … 70 °C; nominal secondary output 0.1429 A.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesLF
Product ReferenceLF 510-S/SP22
Primary Nominal Current500 A
Supply Voltage±14.25 .. ±25.2 V
Measurementcurrent: DC, AC, pulsed...
MountingPanel Mount
Application Domain—
Electrical Data — LF 510-S/SP22
Primary Nominal RMS Current (IPN)500 A
Primary Current, Measuring Range (IPM)0 .. ± 1200 A
Secondary Nominal RMS Current (ISN)0.1429 A
Turns Ratio (NP/NS)1 : 3500
Supply Voltage (UC)±14.25 .. ±25.2 V
Current Consumption (IC)44 + IS mA @ ±UC = ±15 V / 49 + IS mA @ ±UC = ±24 V
Resistance of Secondary Winding (RS)27.7 Ohm
Accuracy & Dynamic Performance
Total Error (εtot) @ IPN± 0.5 % (25 … 70 °C) / ± 0.6 % (−40 … 70 °C)
Linearity Error (εL)± 0.1 %
Electrical Offset Current (IO)± 1 A
Magnetic Offset Current (IO M)± 0.7 A
Delay Time (tD)< 0.5 µs
Frequency Bandwidth (BW)200 kHz
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud4 kV
Impulse Withstand Voltage (1.2/50 µs) UNi10.8 kV
Comparative Tracking Index (CTI)600
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)−40 … 70 °C
Ambient Storage Temperature (TA st)−45 … 90 °C
Mass (m)240 g
Case MaterialV0 according to UL 94
Standards & Certifications
EN 501552021
EN 50124-12017
EN 50121-3-22016
UL 5082010

Note: Specifications are taken from the official LF 510-S/SP22 datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the LF 510-S/SP22 are shown below.

LF 510-S/SP22 outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM LF 510-S/SP22 datasheet
Outline Dimensions & Mechanical Data
Mass240 g
Resistance of Secondary Winding (RS)27.7 Ohm
Case MaterialV0 according to UL 94

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the LF 510-S/SP22.

Single or three phase inverters
Propulsion and braking choppers
Propulsion converters
Auxiliary converters
Battery chargers
Substations

Characteristic Curves

The characteristic curves of the LF 510-S/SP22 from the official datasheet are shown below.

LF 510-S/SP22 characteristic curves
Characteristic curves — source: LEM LF 510-S/SP22 datasheet
Accuracy & Dynamic Characteristics
Total Error (εtot) @ IPN± 0.5 % (25 … 70 °C) / ± 0.6 % (−40 … 70 °C)
Linearity Error (εL)± 0.1 %
Frequency Bandwidth (BW)200 kHz

Note: Refer to the datasheet for the complete set of characteristic curves.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment