LT 1005-T/SP4

Closed loop (compensated)

LEM | LT-Series | Closed loop (compensated) | EN

1000 ANominal Primary Current
± 15 .. 24 VPower Supply
Closed loop (compensated)Technology
DC .. 150 kHzBandwidth (-1dB)
± 0.4 %Overall Accuracy @ IPN

Additional Technical Details

View Full Specifications
Conversion Ratio (KN)1 : 4000
Secondary Nominal RMS Current (ISN)250 mA
Response Time to 90 % of IPN Step< 1 µs
Isolation Test Voltage (50 Hz, 1 min)12 kV
Operating Temperature Range- 40 .. + 85 °C
di/dt Accurately Followed> 50 A/µs

Standards & Approvals

  • EN

Typical Applications

UNVERIFIED.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The LT 1005-T/SP4 is a closed loop (compensated) current transducer from LEM for the electronic measurement of currents: DC, AC, pulsed..., with galvanic isolation.

It offers excellent accuracy, very good linearity, low temperature drift and wide frequency bandwidth. Typical applications include UNVERIFIED.

Key characteristics from the official datasheet: frequency bandwidth DC .. 150 kHz; operating temperature - 40 .. + 85.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesLT
Product ReferenceLT 1005-T/SP4
Primary Nominal Current1000 A
Supply Voltage± 15 .. 24 V
Measurementcurrents: DC, AC, pulsed...
Mounting—
Application Domain—
Electrical Data — LT 1005-T/SP4
Primary Nominal RMS Current (IPN)1000 A
Primary Current, Measuring Range (IPM)@ + 24 V 0
Secondary Nominal RMS Current (ISN)250 mA
Conversion Ratio (KN)1 : 4000
Supply Voltage (UC)± 15 .. 24 V
Current Consumption (IC)30 (@ ± 24 V) + IS mA
Accuracy & Dynamic Performance
Overall Accuracy @ IPN, TA = 25 °C (XG)± 0.4 %
Temperature Variation of IO (Max)± 0.80 mA
Response Time to 90 % of IPN Step (tr)< 1 µs
di/dt Accurately Followed> 50 A/µs
Frequency Bandwidth (-1 dB) (BW)DC .. 150 kHz
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)- 40 .. + 85 °C
Ambient Storage Temperature (TA st)- 40 .. + 95 °C
Secondary Coil Resistance @ TA = 70 °C (RS)26 Ω
Standards & Certifications
EN 50155

Note: Specifications are taken from the official LT 1005-T/SP4 datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the LT 1005-T/SP4 are shown below.

LT 1005-T/SP4 outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM LT 1005-T/SP4 datasheet, page 2

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the LT 1005-T/SP4.

UNVERIFIED

Characteristic Curves

Characteristic curve diagrams are not included in the LT 1005-T/SP4 datasheet; the relevant characteristics are the accuracy and dynamic performance data listed below.

Accuracy & Dynamic Characteristics
Overall Accuracy @ IPN, TA = 25 °C (XG)± 0.4 %
Response Time to 90 % of IPN Step (tr)< 1 µs
di/dt Accurately Followed> 50 A/µs
Frequency Bandwidth (-1 dB) (BW)DC .. 150 kHz

Note: For the full set of performance data, refer to the datasheet.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment