Your Trusted Source for Industrial Electrical Components

LT 208-S7/SP1

Closed loop (compensated)

LEM | LT-Series | EN 50178 | Busbar Mount

200 ANominal Primary Current
± 12 .. 15 VPower Supply
Closed loop (compensated)Technology
DC .. 100 kHzBandwidth (-3dB)
± 0.5 %Overall Accuracy @ IPN

Additional Technical Details

View Full Specifications
Primary Current, Measuring Range0 .. ± 300 A
Conversion Ratio (KN)1 : 2000
Secondary Nominal RMS Current (ISN)100 mA
Response Time to 90 % of IPN Step< 1 µs
Isolation Test Voltage (50 Hz, 1 min)3.52 kV
Impulse Withstand Voltage (1.2/50 µs)6.5 kV

Standards & Approvals

  • EN 50178
  • IEC 61010-1

Typical Applications

AC variable speed drives and servo motor drives, Static converters for DC motor drives, Battery supplied applications, Uninterruptible Power Supplies (UPS), Switched Mode Power Supplies (SMPS), Power supplies for welding applications.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Technical Specifications

General Information
ManufacturerLEM
Product SeriesLT
Product ReferenceLT 208-S7/SP1
Primary Nominal Current200 A
Supply Voltage± 12 .. 15 V
Measurementcurrents: DC, AC, pulsed...
MountingBusbar Mount
Application DomainIndustrial
Electrical Data — LT 208-S7/SP1
Primary Nominal RMS Current (IPN)200 A
Primary Current, Measuring Range (IPM)0 .. ± 300 A
Secondary Nominal RMS Current (ISN)100 mA
Conversion Ratio (KN)1 : 2000
Supply Voltage (UC)± 12 .. 15 V
Current Consumption (IC)28 (@ ± 12 V) + IS mA
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud3.52 kV
Impulse Withstand Voltage (1.2/50 µs) UNi6.5 kV
Creepage Distance (dCp)10 mm
Clearance (dCI)6 mm
Comparative Tracking Index (CTI)275
Rated Insulation Voltage (basic)600 V
Overvoltage Category / Pollution DegreeOver voltage category OV 3 · Pollution degree PD 2
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)- 10 .. + 70 °C
Ambient Storage Temperature (TA st)- 25 .. + 80 °C
Secondary Coil Resistance @ TA = 70 °C (RS)21 Ω
Mass (m)82 g
Standards & Certifications
EN 50178Compliance
IEC 61010-1Compliance

Note: Specifications are taken from the official LT 208-S7/SP1 datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the LT 208-S7/SP1 are shown below.

LT 208-S7/SP1 outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM LT 208-S7/SP1 datasheet
Outline Dimensions & Mechanical Data
Mass82 g

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the LT 208-S7/SP1.

AC variable speed drives and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications

Characteristic Curves

Characteristic curve diagrams are not included in the LT 208-S7/SP1 datasheet; the relevant characteristics are the accuracy and dynamic performance data listed below.

Note: For the full set of performance data, refer to the datasheet.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment