Your Trusted Source for Industrial Electrical Components

LT 505-S/SP5

Closed loop (compensated)

LEM | LT-Series | Closed loop (compensated) | EN 50155

720 ANominal Primary Current
± 24 VPower Supply
Closed loop (compensated)Technology
DC .. 150 kHzBandwidth (-1dB)
± 0.5 %Overall Accuracy @ IPN

Additional Technical Details

View Full Specifications
Primary Current, Measuring Range0 .. ± 1400 A
Conversion Ratio (KN)1 : 5000
Secondary Nominal RMS Current (ISN)144 mA
Isolation Test Voltage (50 Hz, 1 min)6 kV
Operating Temperature Range- 40 .. + 80 °C
di/dt Accurately Followed> 50 A/µs

Standards & Approvals

  • EN 50155

Typical Applications

UNVERIFIED.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The LT 505-S/SP5 is a closed loop (compensated) current transducer from LEM for the electronic measurement of currents: DC, AC, pulsed..., with galvanic isolation.

It offers excellent accuracy, very good linearity, low temperature drift and wide frequency bandwidth. Typical applications include UNVERIFIED.

Key characteristics from the official datasheet: linearity error < 0.1 %; frequency bandwidth DC .. 150 kHz; operating temperature - 40 .. + 80.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesLT
Product ReferenceLT 505-S/SP5
Primary Nominal Current720 A
Supply Voltage± 24 V
Measurementcurrents: DC, AC, pulsed...
Mounting—
Application Domain—
Electrical Data — LT 505-S/SP5
Primary Nominal RMS Current (IPN)720 A
Primary Current, Measuring Range (IPM)0 .. ± 1400 A
Secondary Nominal RMS Current (ISN)144 mA
Conversion Ratio (KN)1 : 5000
Supply Voltage (UC)± 24 V
Current Consumption (IC)30 + I mA • I = 0 .. ± 1400 A
Accuracy & Dynamic Performance
Overall Accuracy @ IPN, TA = 25 °C (XG)± 0.5 %
Linearity Error (εL)< 0.1 %
Offset Current @ IP = 0, TA = 25 °C (IO)± 0.4 mA
Temperature Variation of IO (Max)± 1.0 mA
di/dt Accurately Followed> 50 A/µs
Frequency Bandwidth (-1 dB) (BW)DC .. 150 kHz
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)- 40 .. + 80 °C
Ambient Storage Temperature (TA st)- 50 .. + 85 °C
Mass (m)600 g
Standards & Certifications
EN 50155:

Note: Specifications are taken from the official LT 505-S/SP5 datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the LT 505-S/SP5 are shown below.

LT 505-S/SP5 outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM LT 505-S/SP5 datasheet, page 2
Outline Dimensions & Mechanical Data
Mass600 g

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the LT 505-S/SP5.

UNVERIFIED

Characteristic Curves

Characteristic curve diagrams are not included in the LT 505-S/SP5 datasheet; the relevant characteristics are the accuracy and dynamic performance data listed below.

Accuracy & Dynamic Characteristics
Overall Accuracy @ IPN, TA = 25 °C (XG)± 0.5 %
Linearity Error (εL)< 0.1 %
di/dt Accurately Followed> 50 A/µs
Frequency Bandwidth (-1 dB) (BW)DC .. 150 kHz

Note: For the full set of performance data, refer to the datasheet.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment