Your Trusted Source for Industrial Electrical Components

APR 50 B10

AC Current Transducer APR-B10 I = 10 ... 400 A

LEM | APR-Series | Panel Mount

±0.5 %Linearity Error (Max)
µs 6.1 kVImpulse withstand voltage 1.2/50 (U)
5.5 mmCreepage distance (d)
152Route du Nant-d’Avril
−20 … +60 °CAmbient Operating Temperature (TA)

Additional Technical Details

View Full Specifications
Operating Temperature Range−20 … +60 °C
Isolation Test Voltage4.13 kV
BW Frequency bandwidth (±1 %) 30 …6000 Hz
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud4.13 kV
Rated insulation RMS voltage (U)300 V
RMS voltage for AC insulation test 2) 50 Hz (U)1 min 4.13 kV

Standards & Approvals

Typical Applications

VFD Controlled Loads: VFD output indicates how the motor and attached load are operating, SCR Controlled Loads: Accurate measurement of phase angle fired or burst fired (time proportioned) SCRs. Current measurement gives faster response than temperature measurement, Switching Power Supplies and Electronic Ballasts: True rms sensing is the most accurate way to measure power supply or ballast input power

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The APR 50 B10 is a None current transducer from LEM.

Typical applications include VFD Controlled Loads: VFD output indicates how the motor and attached load are operating, SCR Controlled Loads: Accurate measurement of phase angle fired or burst fired (time proportioned) SCRs. Current measurement gives faster response than temperature measurement and Switching Power Supplies and Electronic Ballasts: True rms sensing is the most accurate way to measure power supply or ballast input power.

Key characteristics from the official datasheet: linearity error ±0.5 %; operating temperature −20 … +60 °C.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesAPR
Product ReferenceAPR 50 B10
Measurement—
MountingPanel Mount
Application DomainEnergies
Accuracy & Dynamic Performance
Linearity Error (εL) (0 ... ±IPN)±0.5 %
BW Frequency bandwidth (±1 %) 30 …6000 Hz
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud4.13 kV
Rated insulation RMS voltage (U)300 V
RMS voltage for AC insulation test 2) 50 Hz (U)1 min 4.13 kV
Impulse withstand voltage 1.2/50 (U)µs 6.1 kV
Creepage distance (d)5.5 mm
Route du Nant-d’Avril152
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)−20 … +60 °C
Ambient Storage Temperature (TA st)−20 … +85 °C
Mass (m)90 g
Case MaterialInsulating plastic case recognized according to UL 94-V0.
Ambient operating temperature −20 … (T)+60 °C
Ambient storage temperature −20 … (T)+85 °C
RH Relative Humidity (non-condensing)≤ 85 %
Altitude above sea level (indoor use only)2000 m
IPxx Protection degree IP20

Note: Specifications are taken from the official APR 50 B10 datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the APR 50 B10 are shown below.

APR 50 B10 outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM APR 50 B10 datasheet, page 4
Outline Dimensions & Mechanical Data
Mass90 g
Case MaterialInsulating plastic case recognized according to UL 94-V0.
IPxx Protection degree IP20

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the APR 50 B10.

VFD Controlled Loads: VFD output indicates how the motor and attached load are operating
SCR Controlled Loads: Accurate measurement of phase angle fired or burst fired (time proportioned) SCRs. Current measurement gives faster response than temperature measurement
Switching Power Supplies and Electronic Ballasts: True rms sensing is the most accurate way to measure power supply or ballast input power

Characteristic Curves

Characteristic curve diagrams are not included in the APR 50 B10 datasheet; the relevant characteristics are the accuracy and dynamic performance data listed below.

Accuracy & Dynamic Characteristics
Linearity Error (εL) (0 ... ±IPN)±0.5 %
BW Frequency bandwidth (±1 %) 30 …6000 Hz

Note: For the full set of performance data, refer to the datasheet.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment