Your Trusted Source for Industrial Electrical Components

HO 50-S-0100

Open loop

LEM | HO-Series | Open loop | IEC 61800-1 | Panel Mount

50 ANominal Primary Current
4.5 ... 5.5 VPower Supply
Open loopTechnology
100 kHzBandwidth (-1dB)
−0.75 ... 0.75 % of IPNLinearity Error (Max)

Additional Technical Details

View Full Specifications
Primary Current, Measuring Range−125 ... 125 A
Output Voltage Range−2 ... 2 V
Supply Voltage4.5 ... 5.5 V
Accuracy @ IPN−1.25 ... 1.25 % of IPN
Operating Temperature Range−40 ... 105 °C
Isolation Test Voltage4.3 kV

Standards & Approvals

  • IEC 61800-1
  • IEC 61800-2
  • IEC 61800-3
  • IEC 61800-5-1
  • IEC 62109-1
  • UL 508: 2013

Typical Applications

AC variable speed and servo motor drives, Static converters for DC motor drives, Battery supplied applications, Uninterruptible Power Supplies (UPS), Switched Mode Power Supplies (SMPS), Power supplies for welding applications, Combiner box, MPPT.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The HO 50-S-0100 is an open loop current transducer from LEM for the electronic measurement of current: DC, AC, pulsed..., with galvanic isolation.

Typical applications include AC variable speed and servo motor drives, Static converters for DC motor drives, Battery supplied applications and Uninterruptible Power Supplies (UPS).

Key characteristics from the official datasheet: linearity error −0.75 ... 0.75 % of IPN; frequency bandwidth 100 kHz; operating temperature −40 ... 105 °C.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesHO
Product ReferenceHO 50-S-0100
Primary Nominal Current50 A
Supply Voltage4.5 ... 5.5 V
Measurementcurrent: DC, AC, pulsed...
MountingPanel Mount
Application DomainIndustrial
Electrical Data — HO 50-S-0100
Primary Nominal RMS Current (IPN)50 A
Primary Current, Measuring Range (IPM)−125 ... 125 A
Supply Voltage (UC)4.5 ... 5.5 V
Current Consumption (IC)19 ... 25 mA
Accuracy & Dynamic Performance
Accuracy @ IPN−1.25 ... 1.25 % of IPN
Linearity Error (εL)−0.75 ... 0.75 % of IPN
Electrical Offset Voltage (VO E) @ IP = 0−5 ... 5 mV
Response Time to 90 % of IPN Step3.5 µs
Frequency Bandwidth100 kHz
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud4.3 kV
Impulse Withstand Voltage (1.2/50 µs) UNi8 kV
Comparative Tracking Index (CTI)600
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)−40 ... 105 °C
Ambient Storage Temperature (TA st)−40 ... 105 °C
Mass (m)32 g
Standards & Certifications
IEC 61800-1Compliance
IEC 61800-2Compliance
IEC 61800-3Compliance
IEC 61800-5-1Compliance
IEC 62109-1Compliance
UL 5082013.

Note: Specifications are taken from the official HO 50-S-0100 datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the HO 50-S-0100 are shown below.

HO 50-S-0100 outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM HO 50-S-0100 datasheet
Outline Dimensions & Mechanical Data
Mass32 g

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the HO 50-S-0100.

AC variable speed and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Combiner box

Characteristic Curves

The characteristic curves of the HO 50-S-0100 from the official datasheet are shown below.

HO 50-S-0100 characteristic curves
Characteristic curves — source: LEM HO 50-S-0100 datasheet
Accuracy & Dynamic Characteristics
Accuracy @ IPN−1.25 ... 1.25 % of IPN
Linearity Error (εL)−0.75 ... 0.75 % of IPN
Response Time to 90 % of IPN Step3.5 µs
Frequency Bandwidth100 kHz

Note: Refer to the datasheet for the complete set of characteristic curves.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment