Your Trusted Source for Industrial Electrical Components

HOP 600-SB

Open loop Hall effect transducer

LEM | HOP-Series | Open loop | EN 50178 | Busbar Mount

±12 ... 15 V D SPower Supply
Open loopTechnology
DC ... 8 kHzBandwidth (-1dB)
6 kVImpulse Withstand Voltage (1.2/50 µs) UNi
250Comparative Tracking Index (CTI)

Additional Technical Details

View Full Specifications
Supply Voltage±12 ... 15 V D S
Operating Temperature Range−10 ... +70 °C
Isolation Test Voltage3 kV
Current Consumption (IC)20 mA 1 01300
Frequency Bandwidth (BW)DC ... 8 kHz
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud3 kV

Standards & Approvals

  • EN 50178
  • UL 508

Typical Applications

Open loop Hall effect transducer, Insulating plastic case recognized according to UL 94-V0. Advantages, Low power consumption, Split core easy for mounting, ontai inH thesei fgiles mhay oti bne adesquatue, colmapletet oir aoccurnate, ndb eprodtucwts depeictede drnawin gst, mhodeles, ned n a the in sp ecifications, and other types of, No insertion losses. LEM Intellectual Property SA Tel. : +86 10 89 45 52 88 pplicatioA 17v 0en 0n u Fe rs ibB oe ua ru gr egard 1 F Fa ax x. :: + +88 66 11 00 88 00 44 88 34 13 20 03 (( osa thle es rs), Power supplies for TELECOM (monitoring & measuring), Uninterruptible Power Supplies (UPS), Switched Mode Power Supplies (SMPS), Battery supplied applications, Electrical chemistry, Chopper.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The HOP 600-SB is an open loop current transducer from LEM for the electronic measurement of currents: DC, AC, pulsed..., with galvanic isolation.

Typical applications include Open loop Hall effect transducer, Insulating plastic case recognized according to UL 94-V0. Advantages, Low power consumption and Split core easy for mounting.

Key characteristics from the official datasheet: frequency bandwidth DC ... 8 kHz; operating temperature −10 ... +70 °C.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesHOP
Product ReferenceHOP 600-SB
Supply Voltage±12 ... 15 V D S
Measurementcurrents: DC, AC, pulsed...
MountingBusbar Mount
Application DomainIndustrial
Electrical Data — HOP 600-SB
Supply Voltage (UC)±12 ... 15 V D S
Current Consumption (IC)20 mA 1 01300
Accuracy & Dynamic Performance
Frequency Bandwidth (BW)DC ... 8 kHz
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud3 kV
Impulse Withstand Voltage (1.2/50 µs) UNi6 kV
Comparative Tracking Index (CTI)250
Rated Insulation Voltage (basic)970 V
Rated Insulation Voltage (reinforced)485 V · 300 V
Overvoltage Category / Pollution DegreeOver voltage category OV · Pollution degree PD2
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)−10 ... +70 °C
Ambient Storage Temperature (TA st)−25 ... +85 °C
Mass (m)110 g
Case MaterialInsulating plastic case recognized according to UL 94-V0.
General Tolerance±0.5 mm
Standards & Certifications
EN 50178Compliance
UL 508Compliance

Note: Specifications are taken from the official HOP 600-SB datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the HOP 600-SB are shown below.

HOP 600-SB outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM HOP 600-SB datasheet, page 3
Outline Dimensions & Mechanical Data
General Tolerance±0.5 mm
Mass110 g
Case MaterialInsulating plastic case recognized according to UL 94-V0.

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the HOP 600-SB.

Low power consumption
Split core easy for mounting
Ontai inH thesei fgiles mhay oti bne adesquatue, colmapletet oir aoccurnate, ndb eprodtucwts depeictede drnawin gst, mhodeles, ned n a the in sp ecifications, and other types of
Power supplies for TELECOM (monitoring & measuring)

Characteristic Curves

Characteristic curve diagrams are not included in the HOP 600-SB datasheet; the relevant characteristics are the accuracy and dynamic performance data listed below.

Accuracy & Dynamic Characteristics
Frequency Bandwidth (BW)DC ... 8 kHz

Note: For the full set of performance data, refer to the datasheet.