Authorized Distributor
?
Closed loop (compensated)
| Primary Current, Measuring Range | 12000 A |
| Supply Voltage | ±22.8 ... ±25.2 V |
| Accuracy @ IPN | −0.06 ... 0.06 % of IPN |
| Isolation Test Voltage | 6.4 kV |
| Primary Nominal RMS Current (IPN) | 4000 A |
| Current Consumption (IC) | 0.22 ... 0.35 A |
IEC 61000-6-2: 2016, IEC 61000-6-3: 2006 + A1 (2010) Safety:, IEC 61010-2-030: 2017, IEC 61010-1:2010/AMD1: 2016, 1) IEC 61869-1: 2007, 1) IEC 61869-2: 2012, 1) IEC 61869-6: 2016. Application Domain, Industrial. these standards as this flux-gate transducer has fundamental.
The ITL 4000-S is a closed loop (compensated) current transducer from LEM for the electronic measurement of current: DC, AC, pulsed..., with galvanic isolation.
Typical applications include IEC 61000-6-2: 2016, IEC 61000-6-3: 2006 + A1 (2010) Safety:, IEC 61010-2-030: 2017 and IEC 61010-1:2010/AMD1: 2016.
Key characteristics from the official datasheet: linearity error −0.01 ... 0.01 % of IPN; frequency bandwidth 50 kHz.
| General Information | |
|---|---|
| Manufacturer | LEM |
| Product Series | ITL |
| Product Reference | ITL 4000-S |
| Primary Nominal Current | 4000 A |
| Supply Voltage | ±22.8 ... ±25.2 V |
| Measurement | current: DC, AC, pulsed... |
| Mounting | — |
| Application Domain | Industrial. these standards as this flux-gate transducer has fundamental |
| Electrical Data — ITL 4000-S | |
|---|---|
| Primary Nominal RMS Current (IPN) | 4000 A |
| Primary Current, Measuring Range (IPM) | 12000 A |
| Supply Voltage (UC) | ±22.8 ... ±25.2 V |
| Current Consumption (IC) | 0.22 ... 0.35 A |
| Accuracy & Dynamic Performance | |
|---|---|
| Accuracy @ IPN | −0.06 ... 0.06 % of IPN |
| Linearity Error (εL) | −0.01 ... 0.01 % of IPN |
| Response Time to 90 % of IPN Step | 10 µs |
| Frequency Bandwidth | 50 kHz |
| Insulation Coordination | |
|---|---|
| RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud | 6.4 kV |
| Impulse Withstand Voltage (1.2/50 µs) UNi | 16.5 kV |
| Comparative Tracking Index (CTI) | 600 |
| Standards & Certifications | |
|---|---|
| IEC 61000-6-2 | Compliance |
| IEC 61000-6-3 | 2006 + A1 (2010) |
Note: Specifications are taken from the official ITL 4000-S datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.
Official technical documentation for the ITL 4000-S.
Outline dimensions, pin layout and connection diagrams of the ITL 4000-S are shown below.
Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.
Typical applications of the ITL 4000-S.
The characteristic curves of the ITL 4000-S from the official datasheet are shown below.
| Accuracy & Dynamic Characteristics | |
|---|---|
| Accuracy @ IPN | −0.06 ... 0.06 % of IPN |
| Linearity Error (εL) | −0.01 ... 0.01 % of IPN |
| Response Time to 90 % of IPN Step | 10 µs |
| Frequency Bandwidth | 50 kHz |
Note: Refer to the datasheet for the complete set of characteristic curves.