Voltage Transducer DVC 1000-P U = 1000 V

LEM | DVC-Series | EN 50155 | PCB Mount

1000 VNominal Primary Voltage
1000 VNominal Primary Current
4.75 ... 5.25 VPower Supply
-0.2 ... 0.2 % of IPNLinearity Error (Max)
-6.00 / Max 6.00 VNominal Primary Voltage

Additional Technical Details

View Full Specifications
Output Voltage Range4.5 voltage
Supply Voltage4.75 ... 5.25 V
Operating Temperature Range-40 ... 85 °C
Isolation Test Voltage4.26 kV
Primary Nominal RMS Current (IPN)1000 V
Current Consumption (IC)29 ... +5 mA

Standards & Approvals

  • EN 50155:
  • EN 50121-3-2:
  • IEC 62497-1:
  • IEC 61000-6-2:
  • IEC 61000-6-3:
  • IEC 61800-3:
  • IEC 61010-1:
  • IEC 61800-5-1:
  • IEC 62109-1:
  • UL 508:

Typical Applications

EN 50155: 2017, EN 50121-3-2: 2016, IEC 62497-1: 2018, IEC 61000-6-2: 2016, IEC 61000-6-3: 2016, IEC 61800-3: 2005, IEC 61010-1: 2010, IEC 61800-5-1: 2007, IEC 62109-1: 2010, UL 508: 2018 Application Domain, Industrial or Railway (fixed installations and onboard). Page 1/12 notice Route du Nant-d'Avril, 152 www.lem.com

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The DVC 1000-P is a None current transducer from LEM for the electronic measurement of voltage: DC, AC, pulsed..., with galvanic isolation, delivering an instantaneous output voltage of Min 0.5 V.

It offers excellent accuracy and low temperature drift. Typical applications include EN 50155: 2017, EN 50121-3-2: 2016, IEC 62497-1: 2018 and IEC 61000-6-2: 2016.

Key characteristics from the official datasheet: linearity error -0.2 ... 0.2 % of IPN; operating temperature -40 ... 85 °C.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesDVC
Product ReferenceDVC 1000-P
Nominal Primary Voltage1000 V
Primary Nominal Current1000 V
Supply Voltage4.75 ... 5.25 V
Measurementvoltage: DC, AC, pulsed...
MountingPCB Mount
Application DomainIndustrial or Railway (fixed installations and onboard)
Electrical Data — DVC 1000-P
Primary Nominal RMS Current (IPN)1000 V
Supply Voltage (UC)4.75 ... 5.25 V
Current Consumption (IC)29 ... +5 mA
Resistance of Primary Winding (RP)12.6 MΩ
Primary nominal DC voltage (continuous) (UPNDC)Typ 1000 V
Primary nominal AC RMS voltage (continuous) (UPNAC)Typ 1000 V
Primary voltage, measuring range (UPM)Min -1500 / Max 1500 V
Load resistance (RL)Min 2000 Ω
Secondary voltage (US)Min 0.5 V
⎓ 1) DC supply voltage (UC)Min 4.75 / Typ 5 / Max 5.25 V
⎓ DC current consumption (IC)Typ 29 mA
Rise time of (10 % ... 90 %) U C (trise)Max 100 ms
Total error (εtot)Min -1.5 %
Temperature variation of referred to primary U O (UOT)Min -3.00 / Max 3.00 V
Electrical offset voltage referred to primary (UOE)Min -6.00 / Max 6.00 V
Sensitivity error (εS)Min -0.8 %
Temperature variation of sensitivity error (εST)Min -0.4 %
Linearity error (εL)Min -0.2 U % of P N
RMS noise voltage 100 Hz … 100 kHz referred to primary (Uno)Typ 450 mV
Delay time to 10 % of the final output value for step U P N (tD10)Typ 1 µs
Delay time to 90 % of the final output value for step U P N (tD90)Typ 8 µs
Start-up time (tstart)Typ 1 ms
Resistance of primary circuit (RP)Typ 12.6 MΩ
Absolute Maximum Ratings
⎓ (U Maximum DC supply voltage = 0 V, 0.1 s) P (UCmax)6 V
Absolute Maximum Ratings
⎓ Maximum DC supply voltage (working) (− 40 … + 85 °C) (UCmax)5.25 V
Absolute Maximum Ratings
Electrostatic discharge voltage (HBM - Human Body Model) (UESDHBM)4 kV
Absolute Maximum Ratings
Maximum DC common mode voltage (UU+HV+HV−|UUand−|HV+HV−)≤ 1.5 kV
Accuracy & Dynamic Performance
Linearity Error (εL)-0.2 ... 0.2 % of IPN
Electrical Offset Voltage (VO E) @ IP = 0-6.00 ... 6.00 V
Response Time to 90 % of IPN Step8 µs
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud4.26 kV
Impulse Withstand Voltage (1.2/50 µs) UNi7.84 kV
Creepage Distance (dCp)9.0 mm
Clearance (dCI)9.0 mm
Comparative Tracking Index (CTI)600
RMS voltage for AC insulation test at 50 Hz (Ud)4.26 kV
Impulse withstand voltage 1.2/50 μs (UNi)7.84 kV
(q Partial discharge RMS test voltage < 10 pC) m (Ut)1650 V
Case materialV0
Application example RMS voltage line-to-neutral600 V
Application example System voltage RMS600 V
Application example Rated insulation RMS voltage (UNm)600 V
Operating voltage1000 V
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)-40 ... 85 °C
Ambient Storage Temperature (TA st)-50 ... 90 °C
Mass (m)22 g
Relative humidity (RH)Max 95 %
Ingress protection ratingTyp IP20
AltitudeMax 1) 2000 m
Pollution degreeMax 2) PD3
Standards & Certifications
EN 50155Compliance
EN 50121-3-2Compliance
IEC 62497-1Compliance
IEC 61000-6-2Compliance
IEC 61000-6-3Compliance
IEC 61800-3Compliance
IEC 61010-1Compliance
IEC 61800-5-1Compliance
IEC 62109-1Compliance
UL 508Compliance

Note: Specifications are taken from the official DVC 1000-P datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the DVC 1000-P are shown below.

DVC 1000-P outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM DVC 1000-P datasheet
Outline Dimensions & Mechanical Data
Mass22 g
Resistance of Primary Winding (RP)12.6 MΩ
Case materialV0
Ingress protection ratingTyp IP20

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the DVC 1000-P.

EN 50155: 2017
EN 50121-3-2: 2016
IEC 62497-1: 2018
IEC 61000-6-2: 2016
IEC 61000-6-3: 2016
IEC 61800-3: 2005
IEC 61010-1: 2010

Characteristic Curves

The characteristic curves of the DVC 1000-P from the official datasheet are shown below.

DVC 1000-P characteristic curves
Characteristic curves — source: LEM DVC 1000-P datasheet
Accuracy & Dynamic Characteristics
Secondary voltage (US)Min 0.5 V
Rise time of (10 % ... 90 %) U C (trise)Max 100 ms
Total error (εtot)Min -1.5 %
Sensitivity error (εS)Min -0.8 %
Temperature variation of sensitivity error (εST)Min -0.4 %
Linearity error (εL)Min -0.2 U % of P N
Response Time to 90 % of IPN Step8 µs
Reference Conditions
Ambient Temperature (TA)25 °C, unless otherwise noted
Output Load Resistance (RL)Min 2000 Ω

Note: Refer to the datasheet for the complete set of characteristic curves.