Your Trusted Source for Industrial Electrical Components
Home Products LEM Voltage Sensors DVL Series DVL 1000/SP1

DVL 1000/SP1

Voltage transducer

LEM | DVL-Series | EN 50155

1000 VNominal Primary Voltage
±13.5 .. ±26.4 VPower Supply
14 kHz (−3 dB)Bandwidth (-1dB)
± 1 % (−40 … 85 °C)Total Error @ IPN
± 0.5 %Linearity Error (Max)

Additional Technical Details

View Full Specifications
Primary Nominal RMS Voltage1000 V
Primary Voltage Measuring Range± 1500 V
Secondary Nominal RMS Current50 mA
Operating Temperature Range−40 … 85 °C
RMS Voltage for AC Insulation Test8.5 kV
Measuring Resistance (RM)0 .. 133 Ohm

Standards & Approvals

  • EN 50155: 2021
  • EN 50178: 1997
  • EN 50124-1: 2017
  • EN 50121-3-2: 2016
  • UL 508: 2013

Typical Applications

AC variable speed and servo motor drives, Static converters for DC motor drives, Battery supplied applications, Uninterruptible Power Supplies (UPS), Switched Mode Power Supplies (SMPS), Power supplies for welding applications, Renewable Energy (Solar and Wind), Single or three phase inverters, Propulsion and braking choppers, Auxiliary converters, High power drives, Substations.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The DVL 1000/SP1 is a None current transducer from LEM for the electronic measurement of voltage: DC, AC, pulsed..., with galvanic isolation.

It offers excellent accuracy. Typical applications include AC variable speed and servo motor drives, Static converters for DC motor drives, Battery supplied applications and Uninterruptible Power Supplies (UPS).

Key characteristics from the official datasheet: total error ± 1 % (−40 … 85 °C); linearity error ± 0.5 %; frequency bandwidth 14 kHz (−3 dB); operating temperature −40 … 85 °C; nominal secondary output 50 mA.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesDVL
Product ReferenceDVL 1000/SP1
Nominal Primary Voltage1000 V
Supply Voltage±13.5 .. ±26.4 V
Measurementvoltage: DC, AC, pulsed...
Mounting—
Application DomainRailway (fixed installations and onboard), Industrial
Electrical Data — DVL 1000/SP1
Primary Nominal RMS Voltage (UPN)1000 V
Primary Voltage, Measuring Range (UPM)± 1500 V
Measuring Resistance (RM)0 .. 133 Ohm
Secondary Nominal RMS Current (ISN)50 mA
Secondary Current (IS)± 75 mA
Supply Voltage (UC)±13.5 .. ±26.4 V
Current Consumption (IC)25 mA @ ±UC = ±24 V
Sensitivity (S)50 µA/V
Resistance of Primary (RP)11.3 MOhm
Total Primary Power Loss0.09 mW
Insulation Resistance (RINS)200 MOhm
Accuracy & Dynamic Performance
Sensitivity Error± 0.2 %
Temperature Variation of Sensitivity Error± 0.5 %
Linearity Error (εL)± 0.5 %
Total Error (εtot)± 1 % (−40 … 85 °C)
RMS Noise Current10 µA
Delay Time @ 10 % of UPN Step30 µs
Delay Time @ 90 % of UPN Step50 .. 60 µs
Frequency Bandwidth (BW)14 kHz (−3 dB)
Start-up Time190 .. 250 ms
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud8.5 kV
Impulse Withstand Voltage (1.2/50 µs) UNi16 kV
Comparative Tracking Index (CTI)600
Partial Discharge Test Voltage (Ut)2700 V
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)−40 … 85 °C
Ambient Storage Temperature (TA st)−50 … 90 °C
Mass (m)270 g
Case MaterialV0 according to UL 94
Standards & Certifications
EN 501552021
EN 501781997
EN 50124-12017
EN 50121-3-22016
UL 5082013

Note: Specifications are taken from the official DVL 1000/SP1 datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the DVL 1000/SP1 are shown below.

DVL 1000/SP1 outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM DVL 1000/SP1 datasheet
Outline Dimensions & Mechanical Data
Mass270 g
Case MaterialV0 according to UL 94

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the DVL 1000/SP1.

AC variable speed and servo motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies (UPS)
Switched Mode Power Supplies (SMPS)
Power supplies for welding applications
Renewable Energy (Solar and Wind)

Characteristic Curves

The characteristic curves of the DVL 1000/SP1 from the official datasheet are shown below.

DVL 1000/SP1 characteristic curves
Characteristic curves — source: LEM DVL 1000/SP1 datasheet
Accuracy & Dynamic Characteristics
Sensitivity (S)50 µA/V
Sensitivity Error± 0.2 %
Temperature Variation of Sensitivity Error± 0.5 %
Linearity Error (εL)± 0.5 %
Total Error (εtot)± 1 % (−40 … 85 °C)
Frequency Bandwidth (BW)14 kHz (−3 dB)

Note: Refer to the datasheet for the complete set of characteristic curves.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment