Your Trusted Source for Industrial Electrical Components
Home Products LEM Voltage Sensors DVL Series DVL 1000/SP5

DVL 1000/SP5

Voltage transducer

LEM | DVL-Series | EN 50155

1000 VNominal Primary Voltage
±13.5 .. ±26.4 VPower Supply
14 kHz (−3 dB)Bandwidth (-1dB)
± 1 % (−40 … 85 °C)Total Error @ IPN
± 0.5 %Linearity Error (Max)

Additional Technical Details

View Full Specifications
Primary Nominal RMS Voltage1000 V
Primary Voltage Measuring Range± 1500 V
Secondary Nominal RMS Current50 mA
Operating Temperature Range−40 … 85 °C
RMS Voltage for AC Insulation Test8.5 kV
Measuring Resistance (RM)0 .. 133 Ohm

Standards & Approvals

  • EN 50155: 2021
  • EN 50178: 1997
  • EN 50124-1: 2017
  • EN 50121-3-2: 2016
  • UL 508: 2013
  • IEC 61010-1:2010/AMD1: 2016

Typical Applications

Auxiliary converters, High power drives, Substations.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The DVL 1000/SP5 is a None current transducer from LEM for the electronic measurement of voltage: DC, AC, pulsed..., with galvanic isolation.

It offers excellent accuracy. Typical applications include Auxiliary converters, High power drives and Substations.

Key characteristics from the official datasheet: total error ± 1 % (−40 … 85 °C); linearity error ± 0.5 %; frequency bandwidth 14 kHz (−3 dB); operating temperature −40 … 85 °C; nominal secondary output 50 mA.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesDVL
Product ReferenceDVL 1000/SP5
Nominal Primary Voltage1000 V
Supply Voltage±13.5 .. ±26.4 V
Measurementvoltage: DC, AC, pulsed...
Mounting—
Application DomainRailway (fixed installations and onboard), Industrial
Electrical Data — DVL 1000/SP5
Primary Nominal RMS Voltage (UPN)1000 V
Primary Voltage, Measuring Range (UPM)± 1500 V
Measuring Resistance (RM)0 .. 133 Ohm
Secondary Nominal RMS Current (ISN)50 mA
Secondary Current (IS)± 75 mA
Supply Voltage (UC)±13.5 .. ±26.4 V
Current Consumption (IC)25 mA @ ±UC = ±24 V
Sensitivity (S)50 µA/V
Resistance of Primary (RP)11.3 MOhm
Total Primary Power Loss0.09 mW
Insulation Resistance (RINS)200 MOhm
Accuracy & Dynamic Performance
Sensitivity Error± 0.2 %
Temperature Variation of Sensitivity Error± 0.5 %
Linearity Error (εL)± 0.5 %
Total Error (εtot)± 1 % (−40 … 85 °C)
RMS Noise Current10 µA
Delay Time @ 10 % of UPN Step30 µs
Delay Time @ 90 % of UPN Step50 .. 60 µs
Frequency Bandwidth (BW)14 kHz (−3 dB)
Start-up Time190 .. 250 ms
Insulation Coordination
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud8.5 kV
Impulse Withstand Voltage (1.2/50 µs) UNi16 kV
Comparative Tracking Index (CTI)600
Partial Discharge Test Voltage (Ut)2700 V
Environmental & Mechanical Characteristics
Ambient Operating Temperature (TA)−40 … 85 °C
Ambient Storage Temperature (TA st)−50 … 90 °C
Mass (m)270 g
Case MaterialV0 according to UL 94
Standards & Certifications
EN 501552021
EN 501781997
EN 50124-12017
EN 50121-3-22016
UL 5082013
IEC 61010-12010/AMD1: 2016

Note: Specifications are taken from the official DVL 1000/SP5 datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the DVL 1000/SP5 are shown below.

DVL 1000/SP5 outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM DVL 1000/SP5 datasheet
Outline Dimensions & Mechanical Data
Mass270 g
Case MaterialV0 according to UL 94

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the DVL 1000/SP5.

Auxiliary converters
High power drives
Substations

Characteristic Curves

The characteristic curves of the DVL 1000/SP5 from the official datasheet are shown below.

DVL 1000/SP5 characteristic curves
Characteristic curves — source: LEM DVL 1000/SP5 datasheet
Accuracy & Dynamic Characteristics
Sensitivity (S)50 µA/V
Sensitivity Error± 0.2 %
Temperature Variation of Sensitivity Error± 0.5 %
Linearity Error (εL)± 0.5 %
Total Error (εtot)± 1 % (−40 … 85 °C)
Frequency Bandwidth (BW)14 kHz (−3 dB)

Note: Refer to the datasheet for the complete set of characteristic curves.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment