Authorized Distributor
?
Voltage Transducer DVM 4000-DT/SP1 U = 4000 V
| Supply Voltage | 16.8 ... 30 V |
| Operating Temperature Range | −40 ... 70 °C |
| Isolation Test Voltage | 12 kV |
| Primary Nominal RMS Current (IPN) | 4000 V |
| Current Consumption (IC) | 50 mA |
| Resistance of Primary Winding (RP) | 25.1 MΩ |
EN 50155: 2021, EN 50121-3-2: 2016, EN 50124-1: 2017, IEC 61010-1: 2010, IEC 61800-1: 1997, IEC 61800-2: 2015, IEC 61800-3: 2004, IEC 61800-5-1: 2007, IEC 62109-1: 2010, UL 347 1): 2016. Application Domain, Industrial, Railway (fixed installations and onboard). Note: 1) When used with UL 347 Isolator N° 92.24.06.420.0. Page 1/13 LEM International SA Chemin des Aulx 8 notice www.lem.com
The DVM 4000-DT/SP1 is a None current transducer from LEM for the electronic measurement of voltage: DC, AC, pulsed..., with galvanic isolation, delivering an instantaneous output voltage of Min 0 / Max 10 V.
It offers excellent accuracy and low temperature drift. Typical applications include EN 50155: 2021, EN 50121-3-2: 2016, EN 50124-1: 2017 and IEC 61010-1: 2010.
Key characteristics from the official datasheet: linearity error −0.5 ... 0.5 % of IPN; operating temperature −40 ... 70 °C.
| General Information | |
|---|---|
| Manufacturer | LEM |
| Product Series | DVM |
| Product Reference | DVM 4000-DT/SP1 |
| Nominal Primary Voltage | 4000 V |
| Primary Nominal Current | 4000 V |
| Supply Voltage | 16.8 ... 30 V |
| Measurement | voltage: DC, AC, pulsed... |
| Mounting | — |
| Application Domain | Industrial, Railway (fixed installations and onboard) |
| Electrical Data — DVM 4000-DT/SP1 | |
|---|---|
| Primary Nominal RMS Current (IPN) | 4000 V |
| Supply Voltage (UC) | 16.8 ... 30 V |
| Current Consumption (IC) | 50 mA |
| Resistance of Primary Winding (RP) | 25.1 MΩ |
| Primary nominal DC voltage (continuous) (UPNDC) | Typ 4000 V |
| Primary nominal AC RMS voltage (continuous) (UPNAC) | Typ 4000 V |
| Primary voltage, measuring range (UPM) | Min 0 / Max 6000 V |
| Measuring resistance (RM) | Min 2000 Ω |
| Secondary nominal RMS voltage (USN) | Typ 6.66 V |
| Secondary voltage (US) | Min 0 / Max 10 V |
| ⎓ DC supply voltage (UC) | Min 16.8 / Max 30 V |
| ⎓ DC current consumption (IC) | Typ 50 mA |
| Rise time of (10 % ... 90 %) U C (trise) | Max 100 ms |
| Total error (εtot) | Min −1 / Max 1 % |
| Electrical offset voltage referred to primary (UOE) | Min −4.2 / Max 4.2 V |
| Temperature variation of referred to primary U O E (UOET) | Min −15 / Max 15 V |
| Sensitivity (S) | Typ 1.66 mV/V |
| Sensitivity error (εS) | Min −0.3 / Max 0.3 % |
| Temperature variation of sensitivity error (εTS) | Min −0.5 / Max 0.5 % |
| Linearity error (εL) | Min −0.5 / Max 0.5 U % of P M |
| RMS noise current 100 Hz ... 100 kHz referred to secondary (Uno) | Typ 2.4 mV |
| Start-up time (tstart) | Typ 190 / Max 250 ms |
| Resistance of primary (RP) | Typ 25.1 MΩ |
| Absolute Maximum Ratings | |
|---|---|
| ⎓ Maximum DC supply voltage (U = 0 V, 0.1 s) P (ÛCmax) | 34.6 V |
| Absolute Maximum Ratings | |
|---|---|
| ⎓ Maximum DC supply voltage (working) (− 40 … + 85 °C) (UCmax) | 30 V |
| Absolute Maximum Ratings | |
|---|---|
| Electrostatic discharge voltage (HBM - Human Body Model) (UESDHBM) | 4 kV |
| Absolute Maximum Ratings | |
|---|---|
| Maximum DC common mode voltage (UU+HV+HV−|UUand−|HV+HV−) | ≤ 6.3 U ≤ P M kV |
| Accuracy & Dynamic Performance | |
|---|---|
| Linearity Error (εL) | −0.5 ... 0.5 % of IPN |
| Electrical Offset Voltage (VO E) @ IP = 0 | −4.2 ... 4.2 V |
| Response Time to 90 % of IPN Step | 50 ... 60 µs |
| Insulation Coordination | |
|---|---|
| RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud | 12 kV |
| Impulse Withstand Voltage (1.2/50 µs) UNi | 30 kV |
| Creepage Distance (dCp) | 101 mm |
| Clearance (dCI) | 74 mm |
| Comparative Tracking Index (CTI) | 600 |
| Mean failure rate (λ) | Typ 1/1827550 h−1 |
| RMS voltage for AC insulation test, 50 Hz, 1 min (Ud) | 12 kV |
| Impulse withstand voltage 1.2/50 μs (UNi) | 30 kV |
| (q Partial discharge RMS test voltage < 10 pC) m (Ut) | 5000 V |
| Case material | V0 |
| Application example RMS voltage line-to-neutral | 1000 V |
| Application example System voltage RMS | 3600 V |
| Application example Rated insulation RMS voltage (UNm) | 4800 V |
| Application example Rated insulation RMS voltage | 1000 V |
| Primary high threshold (UPH) | Typ 500 V |
| Primary low threshold voltage (UPL) | Typ 400 V |
| Maximum secondary (output) threshold detection is active (USTh) | Max 30 V |
| Maximum secondary (output) threshold detection is active (ISTh) | Max 100 mA |
| Minimum load resistance, (RLTh) | Min 300 Ω |
| Delay time of threshold (tDH) | Typ 2 ms |
| Delay time of threshold (tDL) | Typ 700 ms |
| Environmental & Mechanical Characteristics | |
|---|---|
| Ambient Operating Temperature (TA) | −40 ... 70 °C |
| Ambient Storage Temperature (TA st) | −50 ... 90 °C |
| Mass (m) | 375 g |
| Relative humidity (RH) | Max 95 % |
| Ingress protection rating | Typ IP40 |
| Pollution degree | Max PD4 |
| Altitude | Max 1) 2000 m |
| Impact rating | Typ IK06 |
| Standards & Certifications | |
|---|---|
| EN 50155 | Compliance |
| EN 50121-3-2 | Compliance |
| EN 50124-1 | Compliance |
| IEC 61010-1 | Compliance |
| IEC 61800-1 | Compliance |
| IEC 61800-2 | Compliance |
| IEC 61800-3 | Compliance |
| IEC 61800-5-1 | Compliance |
| IEC 62109-1 | Compliance |
| UL 347 | 1): 2016. |
Note: Specifications are taken from the official DVM 4000-DT/SP1 datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.
Official technical documentation for the DVM 4000-DT/SP1.
Outline dimensions, pin layout and connection diagrams of the DVM 4000-DT/SP1 are shown below.
| Outline Dimensions & Mechanical Data | |
|---|---|
| Mass | 375 g |
| Resistance of Primary Winding (RP) | 25.1 MΩ |
| Case material | V0 |
| Ingress protection rating | Typ IP40 |
Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.
Typical applications of the DVM 4000-DT/SP1.
The characteristic curves of the DVM 4000-DT/SP1 from the official datasheet are shown below.
| Accuracy & Dynamic Characteristics | |
|---|---|
| Secondary voltage (US) | Min 0 / Max 10 V |
| Rise time of (10 % ... 90 %) U C (trise) | Max 100 ms |
| Total error (εtot) | Min −1 / Max 1 % |
| Sensitivity (S) | Typ 1.66 mV/V |
| Sensitivity error (εS) | Min −0.3 / Max 0.3 % |
| Temperature variation of sensitivity error (εTS) | Min −0.5 / Max 0.5 % |
| Linearity error (εL) | Min −0.5 / Max 0.5 U % of P M |
| Response Time to 90 % of IPN Step | 50 ... 60 µs |
| Reference Conditions | |
|---|---|
| Ambient Temperature (TA) | 25 °C, unless otherwise noted |
| Output Load Resistance (RL) | Min 300 Ω |
Note: Refer to the datasheet for the complete set of characteristic curves.