Your Trusted Source for Industrial Electrical Components
Home Products LEM Voltage Sensors DVL Series DVL 500-UI

DVL 500-UI

Voltage Transducer

LEM | DVL-Series | EN 50155

500 VNominal Primary Voltage
±13.5 .. ±24 VPower Supply
± 120 % (−25 … 85 °C) / ± 150 % (−40 … 85 °C) / ± 0.5 % (25 °C) / ± 1 % (−40 … 85 °C)Total Error @ IPN
± 0.5 %Linearity Error (Max)
± 120 % (−25 … 85 °C) / ± 150 % (−40 … 85 °C) / ± 0.5 % (25 °C) / ± 1 % (−40 … 85 °C)Total Error (εtot) @ IPN

Additional Technical Details

View Full Specifications
Primary Nominal DC Voltage (UPN DC)500 V
Measuring Resistance (RM)0 .. 555 Ohm
Secondary Nominal DC Current (ISN DC)4 .. 20 mA
Maximum Secondary DC Current (IS max)3 .. 21 mA
Supply Voltage (UC)±13.5 .. ±26.4 V
Rise Time of UC (10 … 90 %)100 ms

Standards & Approvals

  • EN 50155: 2021
  • EN 50178: 1997
  • EN 50124-1: 2017
  • EN 50121-3-2: 2016

Typical Applications

Substations, Trackside.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Product Description

The DVL 500-UI is a None current transducer from LEM for the electronic measurement of voltage: DC, pulsed..., with galvanic isolation.

It offers excellent accuracy. Typical applications include Substations and Trackside.

Key characteristics from the official datasheet: total error ± 120 % (−25 … 85 °C) / ± 150 % (−40 … 85 °C) / ± 0.5 % (25 °C) / ± 1 % (−40 … 85 °C); linearity error ± 0.5 %; operating temperature −40 … 85 °C.

Technical Specifications

General Information
ManufacturerLEM
Product SeriesDVL
Product ReferenceDVL 500-UI
Nominal Primary Voltage500 V
Supply Voltage±13.5 .. ±24 V
Measurementvoltage: DC, pulsed...
Mounting—
Application DomainIndustrial
Primary Nominal DC Voltage (UPN DC)500 V
Measuring Resistance (RM)0 .. 555 Ohm
Secondary Nominal DC Current (ISN DC)4 .. 20 mA
Maximum Secondary DC Current (IS max)3 .. 21 mA
Supply Voltage (UC)±13.5 .. ±26.4 V
Rise Time of UC (10 … 90 %)100 ms
Current Consumption (IC)25 .. 30 mA @ ±U_C = ±24 V
Offset Current Referred to Primary (IO)± 50 µA
Temperature Variation of IO± 150 µA
Resistance of Primary (RP)2.7 MOhm
Insulation Resistance (RINS)200 MOhm
Sensitivity Error± 0.2 %
Temperature Variation of Sensitivity Error± 0.5 %
Linearity Error (εL)± 0.5 %
Total Error (εtot)± 1 %
RMS Noise Current (Ino)10 µA
Delay Time @ 10 % of UPN Step30 µs
Delay Time @ 90 % of UPN Step50 .. 60 µs
Frequency Bandwidth14 kHz (−3 dB)
Start-up Time190 .. 250 ms
RMS Voltage for AC Insulation Test (50 Hz, 1 min) Ud8.5 kV
Impulse Withstand Voltage (1.2/50 µs) UNi16 kV
Insulation Resistance (RINS)200 MOhm
Comparative Tracking Index (CTI)600
Ambient Operating Temperature (TA)−40 … 85 °C
Ambient Storage Temperature (TA st)−50 … 90 °C
Equipment Operating Temperature Class (EN 50155)OT6
Switch-on Extended Operating Temperature Class (EN 50155)ST0
Rapid Temperature Variation Class (EN 50155)H2
Conformal Coating Type (EN 50155)PC2
Mass (m)290 g

Note: Specifications are taken from the official DVL 500-UI datasheet. Parameters that could not be confirmed from the datasheet are marked UNVERIFIED.

Dimensions & Drawings

Outline dimensions, pin layout and connection diagrams of the DVL 500-UI are shown below.

DVL 500-UI outline dimensions and pin layout
Outline dimensions (in mm) and connection diagrams — source: LEM DVL 500-UI datasheet
Outline Dimensions & Mechanical Data
Mass290 g

Note: All dimensions are in millimetres. Refer to the official datasheet for the complete dimension drawing.

Typical Applications

Typical applications of the DVL 500-UI.

Substations
Trackside

Characteristic Curves

The characteristic curves of the DVL 500-UI from the official datasheet are shown below.

DVL 500-UI characteristic curves
Characteristic curves — source: LEM DVL 500-UI datasheet
Accuracy & Dynamic Characteristics
Rise Time of UC (10 … 90 %)100 ms
Sensitivity Error± 0.2 %
Temperature Variation of Sensitivity Error± 0.5 %
Linearity Error (εL)± 0.5 %
Total Error (εtot)± 1 %
Frequency Bandwidth14 kHz (−3 dB)

Note: Refer to the datasheet for the complete set of characteristic curves.

12-Hour RFQ ResponseTimely quotation assistance
Documentation SupportDatasheets & traceability records
Worldwide DeliveryInternational logistics coordination
Order Follow-UpUpdates on lead times & shipment