Eaton | Contactors | 139556

95 AAmperage
1000 VVoltage
950 ABreaking Capacity
160 kWRated Power
ContactorsProduct Type

Additional Technical Details

View Full Specifications
Product Weight7.1 kg
Product Length/Depth208 mm
Product Height189 mm
Product Width140 mm
Degree Of ProtectionIP00
ConnectionScrew terminals

Standards & Approvals

  • tested for category 1 class B CE marking

Typical Applications

Motor Control, Pumps & Fans, HVAC Systems and more.

We respond to RFQs within 12 hours.
0 / 500

Sample requests are subject to manual review.

Why Buy from SafeCirk?

Authorized DistributorLEM & Bussmann
12+ Years of ExperienceIndustrial component supply
Technical SupportProduct selection & applications
Reliable SupplyLead-time & delivery support

Technical Specifications

General Information
Product NameEaton Moeller® series DILM Contactor
Catalog Number139556
Model CodeDILM300A/22(RA250)
EAN4015081363346
Product categoryContactors
Voltage typeAC/DC
Short-circuit protection rating (type 1 coordination) at 1000 V200 A gG/gL
Short-circuit protection rating (type 1 coordination) at 400 V500 A gG/gL
Short-circuit protection rating (type 1 coordination) at 690 V400 A gG/gL
Short-circuit protection rating (type 2 coordination) at 1000 V160 A gG/gL
Short-circuit protection rating (type 2 coordination) at 400 V400 A gG/gL
Short-circuit protection rating (type 2 coordination) at 690 V315 A gG/gL
Electrical Characteristics
Conventional thermal current Ith (1-pole, enclosed)788 A
Conventional thermal current Ith (3-pole, enclosed)315 A
Conventional thermal current Ith at 40°C (3-pole, open)490 A
Conventional thermal current Ith at 50°C (3-pole, open)438 A
Conventional thermal current Ith at 55°C (3-pole, open)418 A
Conventional thermal current Ith at 60°C (3-pole, open)400 A
Conventional thermal current Ith of main contacts (1-pole, open)1000 A
10.11 Short-circuit ratingIs the panel builder's responsibility. The specifications for the switchgear must be observed.
10.2.2 Corrosion resistanceMeets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heatMeets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiationMeets the product standard's requirements.
10.9.2 Power-frequency electric strengthIs the panel builder's responsibility.
10.9.3 Impulse withstand voltageIs the panel builder's responsibility.
Equipment heat dissipation, current-dependent Pvid21 W
Heat dissipation capacity Pdiss0 W
Heat dissipation per pole, current-dependent Pvid7 W
Rated operational current for specified heat dissipation (In)300 A
Static heat dissipation, non-current-dependent Pvs5.5 W
Inrush currentMax. 30 x Ie (peak)
Rated breaking capacity at 1000 V950 A
Rated breaking capacity at 220/230 V3000 A
Rated breaking capacity at 380/400 V3000 A
Rated breaking capacity at 500 V3000 A
Rated breaking capacity at 660/690 V3000 A
Rated insulation voltage (Ui)1000 V
Rated making capacity (cos phi to IEC/EN 60947)3000 A
Rated operational current (Ie)177 A at 690 V (Individual compensation, three-phase capacitors, open) 307 A at up to 525 V (Individual compensation, three-phase capacitors, open)
Rated operational current (Ie) at AC-1, 380 V, 400 V, 415 V490 A
Rated operational current (Ie) at AC-3, 1000 V95 A
Rated operational current (Ie) at AC-3, 220 V, 230 V, 240 V300 A
Rated operational current (Ie) at AC-3, 380 V, 400 V, 415 V300 A
Rated operational current (Ie) at AC-3, 440 V300 A
Rated operational current (Ie) at AC-3, 500 V300 A
Rated operational current (Ie) at AC-3, 660 V, 690 V185 A
Rated operational current (Ie) at AC-4, 1000 V76 A
Rated operational current (Ie) at AC-4, 220 V, 230 V, 240 V240 A
Rated operational current (Ie) at AC-4, 440 V240 A
Rated operational current (Ie) at AC-4, 500 V240 A
Rated operational current (Ie) at AC-4, 660 V, 690 V150 A
Rated operational power at AC-3, 1000 V, 50 Hz132 kW
Rated operational power at AC-3, 240 V, 50 Hz100 kW
Rated operational power at AC-3, 380/400 V, 50 Hz160 kW
Rated operational power at AC-3, 415 V, 50 Hz175 kW
Rated operational power at AC-3, 440 V, 50 Hz185 kW
Rated operational power at AC-3, 500 V, 50 Hz210 kW
Rated operational power at AC-3, 690 V, 50 Hz170 kW
Rated operational power at AC-4, 1000 V, 50 Hz108 kW
Rated operational power at AC-4, 220/230 V, 50 Hz75 kW
Rated operational power at AC-4, 240 V, 50 Hz82 kW
Rated operational power at AC-4, 415 V, 50 Hz142 kW
Rated operational power at AC-4, 440 V, 50 Hz150 kW
Rated operational power at AC-4, 500 V, 50 Hz170 kW
Rated operational power at AC-4, 660/690 V, 50 Hz137 kW
Rated operational voltage (Ue) at AC - max1000 V
Safe isolation1000 V AC, Between coil and contacts, According to EN 61140
Lifespan, electrical100,000 Operations (at Condensor operation)
Lifespan, mechanical10,000,000 Operations (DC operated) 10,000,000 Operations (AC operated)
Operating frequency3000 mechanical Operations/h (DC operated) 200 Operations/h 3000 mechanical Operations/h (AC operated)
Overvoltage categoryIII
Rated impulse withstand voltage (Uimp)8000 V AC
Resistance500 mΩ (Admissible transitional contact resistance - of the external control circuit device when actuating A11)
Shock resistance10 g, N/O main contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 10 g, N/O auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms 8 g, N/C auxiliary contact, Mechanical, according to IEC/EN 60068-2-27, Half-sinusoidal shock 10 ms
Utilization categoryAC-1: Non-inductive or slightly inductive loads, resistance furnaces AC-3: Normal AC induction motors: starting, switch off during running AC-4: Normal AC induction motors: starting, plugging, reversing, inching
Drop-out voltageAC operated: 0.2 x US max - 0.6 x US min, AC operated 0.2 x US max - 0.6 x US min, DC operated
Duty factor100 %
Pick-up voltage0.7 - 1.15 V AC x Us 0.7 - 1.15 V DC x Us
Power consumption110 kW Control transformer with uk ≤ 6%
Power consumption, pick-up, 50 Hz240 VA, Pull-in power, Coil in a cold state and 1.0 x Us
Power consumption, pick-up, 60 Hz240 VA, Pull-in power, Coil in a cold state and 1.0 x Us
Power consumption, sealing, 50 Hz5.5 W, Coil in a cold state and 1.0 x Us 10.5 VA, Coil in a cold state and 1.0 x Us
Power consumption, sealing, 60 Hz10.5 VA, Coil in a cold state and 1.0 x Us 5.5 W, Coil in a cold state and 1.0 x Us
Rated control supply voltage (Us) at AC, 50 Hz - max250 V
Rated control supply voltage (Us) at AC, 50 Hz - min110 V
Rated control supply voltage (Us) at AC, 60 Hz - max250 V
Rated control supply voltage (Us) at AC, 60 Hz - min110 V
Rated control supply voltage (Us) at DC - max250 V
Rated control supply voltage (Us) at DC - min110 V
Assigned motor power at 200/208 V, 60 Hz, 3-phase100 HP
Assigned motor power at 230/240 V, 60 Hz, 3-phase125 HP
Assigned motor power at 460/480 V, 60 Hz, 3-phase250 HP
Assigned motor power at 575/600 V, 60 Hz, 3-phase300 HP
Short-circuit current rating (basic rating)700 A, max. Fuse, SCCR (UL/CSA) 600 A, max. CB, SCCR (UL/CSA) 18 kA, SCCR (UL/CSA)
Short-circuit current rating (high fault at 480 V)250 A, max. CB, SCCR (UL/CSA) 18 kA, Fuse, SCCR (UL/CSA) 700 A, Class L, max. Fuse, SCCR (UL/CSA) 65 kA, CB, SCCR (UL/CSA) 700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA) 18/100 kA, Fuse, SCCR (UL/CSA)
Short-circuit current rating (high fault at 600 V)700 A, Class J, max. Fuse, SCCR (UL/CSA) 18 kA, CB, SCCR (UL/CSA) 18 kA, Fuse, SCCR (UL/CSA) 600 A, max. CB, SCCR (UL/CSA) 700 A, Class L/450 A, Class J, max. Fuse, SCCR (UL/CSA) 18/100 kA, Fuse, SCCR (UL/CSA)
Switching capacity (auxiliary contacts, general use)15 A, 600 V AC, (UL/CSA) 1 A, 250 V DC, (UL/CSA)
Switching capacity (auxiliary contacts, pilot duty)A600, AC operated (UL/CSA) P300, DC operated (UL/CSA)
Switching capacity (main contacts, general use)350 A, Maximum motor rating (UL/CSA)
Mechanical & Physical
Product Length/Depth208 mm
Product Height189 mm
Product Width140 mm
Product Weight7.1 kg
Number of auxiliary contacts (normally closed contacts)2
Number of auxiliary contacts (normally open contacts)2
Number of contacts (normally closed contacts)2
Number of contacts (normally open contacts)2
10.3 Degree of protection of assembliesDoes not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shockDoes not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connectionsIs the panel builder's responsibility.
10.8 Connections for external conductorsIs the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating materialIs the panel builder's responsibility.
ConnectionScrew terminals
Degree of protectionIP00
Fitted with:Suppressor circuit in actuating electronics
ProtectionFinger and back-of-hand proof with terminal shroud or terminal block, Protection against direct contact when actuated from front (EN 50274)
Switching time (AC operated, make contacts, closing delay) - max100 ms
Switching time (AC operated, make contacts, opening delay) - max110 ms
Screw sizeM3.5, Terminal screw, Control circuit cables M10, Terminal screw, Main connections
Screwdriver size2, Terminal screw, Control circuit cables, Pozidriv screwdriver
Terminal capacity (busbar)25 mm width, Main connection
Terminal capacity (copper band)Fixing with flat cable terminal or cable terminal blocks; See terminal capacity for cable terminal blocks
Terminal capacity (flexible with cable lug)50 - 240 mm²
Terminal capacity (flexible with ferrule)2 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.75 - 2.5) mm², Control circuit cables
Terminal capacity (solid)2 x (0.75 - 2.5) mm², Control circuit cables 1 x (0.75 - 2.5) mm², Control circuit cables
Terminal capacity (solid/stranded AWG)2/0 - 500 MCM, Main cables 18 - 14, Control circuit cables
Terminal capacity (stranded with cable lug)70 - 240 mm²
Tightening torque24 Nm, Main cable connection screw/bolt 1.2 Nm, Screw terminals, Control circuit cables
Width across flats16 mm
Environmental & Compliance
CertificationsVDE 0660 UL File No.: E29096 UL Category Control No.: NLDX UL 60947-4-1 IEC/EN 60947-4-1 CSA Class No.: 3211-04 UL/CSA CSA File No. 1017510 North America (UL listed, CSA certified) EN 45545: Fire protection on railway vehicles IEC 61373: Vibration and shock, tested for category 1 class B CE marking
AltitudeMax. 2000 m
Ambient operating temperature - max60 °C
Ambient storage temperature - max80 °C
Ambient operating temperature - min-40 °C
Ambient operating temperature (enclosed) - max40 °C
Ambient operating temperature (enclosed) - min-40 °C
Ambient storage temperature - min-40 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30 Damp heat, constant, to IEC 60068-2-78
10.10 Temperature riseThe panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Pollution degree3
Additional Specifications
Catalog NotesContacts according to EN 50012EN 45545 - Fire protection on railway vehicles: Fire protection class of all plastics according to UL94: V-0 / plastic weight in total: 1.872 kgConventional thermal current Ith of main contacts (1-pole, open) at 60°
10.12 Electromagnetic compatibilityIs the panel builder's responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical functionThe device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.3.1 Verification of thermal stability of enclosuresMeets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effectsMeets the product standard's requirements.
10.2.5 LiftingDoes not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impactDoes not apply, since the entire switchgear needs to be evaluated.
10.2.7 InscriptionsMeets the product standard's requirements.
10.4 Clearances and creepage distancesMeets the product standard's requirements.
10.6 Incorporation of switching devices and componentsDoes not apply, since the entire switchgear needs to be evaluated.
Special purpose rating of definite purpose rating2160 A, LRA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) 1800 A, LRA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) 300 A, FLA 600 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA) 360 A, FLA 480 V 60 Hz 3-ph, 100,000 cycles acc. to UL 1995, (UL/CSA)
AccessoriesFitting options auxiliary contacts: on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA
ApplicationContactors for Motors
Electromagnetic compatibilityDesigned for operation in industrial environments. Its use in residential environments may cause radio-frequency interference, requiring additional noise suppression.
Signal level5 V - 15 V, PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2), Magnet systems
Behavior in marginal and transitional conditionsSealing - Pick-up phase (0.7 x Uc min - 1.15 x Uc max): Contactor switches on with certainty Sealing - Voltage drops (0.2 - 0.6 x Uc min) > 12 ms: Drop-out of the contactor Sealing - Voltage drops (0.6 - 0.7 x Uc min: Contactor remains switched on Sealing - Voltage interruptions 0 - 0.2 x Uc min) > 10 ms: Drop-out of the contactor Sealing - Excess voltage (1.15 - 1.3 x Uc max): Contactor remains switched on Sealing - Pick-up phase (0 - 0.7 x Uc min: Contactor does not switch on Sealing - Voltage drops (0.2 - 0.6 x Uc min ≤12 ms: Time is bridged successfully Sealing - Voltage interruptions (0 - 0.2 x Uc min ≤ 10 ms: Time is bridged successfully

Note: Specifications are taken from the official Eaton DILM300 datasheet.

Documents & Downloads

Official technical documentation for the DILM300.

Typical Applications

Typical applications of the DILM300.

Motor Control
Pumps & Fans
HVAC Systems
Compressors