Authorized Distributor
?
Z-SCH contactor
| Product Weight | 0.14 kg |
| Product Length/Depth | 85 mm |
| Product Height | 65 mm |
| Product Width | 17.7 mm |
Motor control and switching in industrial automation and power distribution panels.
Eaton Z-SCH Installation contactor, 24VAC/50Hz, 2N/C, 25A
Key technical data includes Features: Additional equipment possible; Amperage Rating: 25 A; 10.2.2 Corrosion resistance: Meets the product standard's requirements..
| General Information | |
|---|---|
| Product Name | Eaton Z-SCH contactor |
| Catalog Number | 193984 |
| Model Code | Z-SCH24/1/25-02 |
| EAN | 9010238043800 |
| Product Length/Depth | 85 mm |
| Product Height | 65 mm |
| Product Width | 17.7 mm |
| Product Weight | 0.14 kg |
| Compliances | RoHS conform |
| Amperage Rating | 25 A |
| Standards & Design Verification | |
|---|---|
| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
| 10.11 Short-circuit rating | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.12 Electromagnetic compatibility | Is the panel builder's responsibility. The specifications for the switchgear must be observed. |
| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
| 10.2.2 Corrosion resistance | Meets the product standard's requirements. |
| 10.2.3.1 Verification of thermal stability of enclosures | Meets the product standard's requirements. |
| 10.2.3.2 Verification of resistance of insulating materials to normal heat | Meets the product standard's requirements. |
| 10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects | Meets the product standard's requirements. |
| 10.2.4 Resistance to ultra-violet (UV) radiation | Meets the product standard's requirements. |
| 10.2.5 Lifting | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.6 Mechanical impact | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.2.7 Inscriptions | Meets the product standard's requirements. |
| 10.3 Degree of protection of assemblies | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.4 Clearances and creepage distances | Meets the product standard's requirements. |
| 10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
| 10.7 Internal electrical circuits and connections | Is the panel builder's responsibility. |
| 10.8 Connections for external conductors | Is the panel builder's responsibility. |
| 10.9.2 Power-frequency electric strength | Is the panel builder's responsibility. |
| 10.9.3 Impulse withstand voltage | Is the panel builder's responsibility. |
| 10.9.4 Testing of enclosures made of insulating material | Is the panel builder's responsibility. |
| Equipment heat dissipation, current-dependent | 4.2 W |
| Heat dissipation per pole, current-dependent | 3 W |
| Rated operational current for specified heat dissipation (In) | 25 A |
| Electrical Characteristics | |
|---|---|
| Incandescent lamp load - max | 3000 W |
| Load fluorescent lamp - max | 1160 VA |
| Load fluorescent lamp (duo circuit) - max | 2552 VA |
| Load fluorescent lamp (parallel compensated) - max | 1044 VA |
| Rated operating voltage (Ue) - max | 440 V |
| Rated operating voltage (Ue) - min | 440 V |
| Voltage rating (excitation) - max | 26.4 V |
| Voltage rating (excitation) - min | 20.4 V |
| Voltage type | AC |
| Mechanical & Physical | |
|---|---|
| Built-in depth | 60 mm |
| Degree of protection | IP20 |
| Number of contacts (normally closed contacts) | 2 |
| Number of contacts (normally open contacts) | 0 |
| Number of modular spacings | 1 |
| Utility category | 1 |
| Utilization category (according to EN IEC 60947-4-1) | AC-1 |
| Additional Specifications | |
|---|---|
| Features | Additional equipment possible |
Note: Specifications are taken from the official Eaton Z-SCH24/1/25-02 product data sheet.
Official technical documentation for the Z-SCH24/1/25-02.
Typical applications of the Z-SCH24/1/25-02.